background image

Description

The  DPG1000L is a 2-wire pressure transmitter with
digital display. It is powered by the 4-20 mA current loop
and produces a true analog output signal. The output is
filtered to improve noise immunity. The temperature
compensated piezoresistive transducer features 316
stainless steel wetted parts.

Installation Precautions

Tighten/remove with wrench on hex fitting only. Do not
attempt to rotate gauge by turning housing. Use fittings
appropriate for the pressure range of the gauge. Do not
apply vacuum to gauges not designed for vacuum
operation. NEVER insert objects into the gauge port or
blow out with compressed air. Permanent damage not
covered by warranty will result.

Electrical Connection

Connection to the DPG1000L is made with the 2-wire
cable at the gauge rear. Connect the loop (+) supply to
the RED lead and the loop (–) supply to the BLACK
lead. Reversing the connections will not harm the gauge
but the gauge will not operate with incorrect polarity.

Loop Voltage

Select a loop power supply voltage and total loop
resistance so that when the loop current is 20 mA, the
gauge will have at least 8 VDC at its terminals. Too large
a loop resistance will cause the gauge output to “limit” or
saturate before reaching its full 20 mA output. See graph
below.

The minimum loop supply voltage may be calculated
from the formula:

Vmin = 8V + (20mA x Total loop resistance)

If the terminal voltage of the gauge falls below about 7.8
VDC erroneous reading or erratic operation may occur.
This is indicates that the loop supply/resistance may not
have adequate headroom for reliable operation. This
should never occur in normal use. If it does, check loop
supply and resistance.

Operation

The  DPG1000L is designed for continuous operation.
Warm-up time is negligible. The display will show the
system pressure/vacuum, and the loop current also will
be proportional to the system pressure/vacuum; 4 mA =
Zero or low end, 20 mA = Span, full-scale or high end.

TEST Button

When the TEST button is held depressed, the display
and loop current are switched to a test level determined
by the setting of the Test potentiometer. This test mode
will allow setup and testing of the current loop by
switching to this test level whenever desired without
having to alter the system pressure.

To set the test output level, see gauge label for location
of Test potentiometer. Press and hold the front-panel
TEST button and adjust the Test potentiometer to set the
display and loop current to the desired test level.

Calibration

See gauge label for location of individual controls to
adjust the zero and span of the display.

GAUGE reference units may be re-zeroed without
affecting the span calibration. The gauge port must be
open to the ambient with no pressure or vacuum
applied. Adjust the Zero control until the gauge reads
zero with the minus (–) sign occasionally flashing.

Span calibration should only be attempted if the user
has access to a pressure reference of known accuracy.
The calibration equipment should be at least four times
the gauge accuracy. Zero calibration must be done
before span calibration. Record readings at three to five
points over the range of gauge and adjust span control
to minimize error and meet specifications.

ABSOLUTE reference gauges require vacuum
generation and atmospheric pressure measurement
equipment for accurate calibration and thus are more
difficult to calibrate in the field. Gauges may be returned
to Omega Engineer ing for recalibration. N.I.S.T.
traceability is available.

The  DPG1000L has internal controls to adjust the
agreement between the displayed value and the 4-20
mA loop current. These are set at the factory and should
not normally be adjusted. If adjustment is necessary, the
display zero/span must be accurately set first. Then,
after removing the rear cover, the Loop Zero and Loop
Span controls may be trimmed for 4.00 mA of loop
current at the low end of the range, and 20.00 mA at the
high end of the range, respectively. Accurate pressure
generation and measurement and current measurement
equipment are required to successfully complete this
calibration.

Digital Pressure Gauges

DPG1000L Series, 4-20mA Current Loop Powered

INSTRUCTION

SHEET

M3360/1001

SPECIFICATIONS

Ranges & Resolution

30.0 inHg vacuum, ±15.00, 3.00, 5.00, 15.00, 30.0 psig
100.0, 199.9, 300, 500, 1000, 3000, 5000 psig
Absolute reference: 15.00, 100.0 psia

Optional Units

Most engineering units such as kPa, atm, bar, mbar,
inHg, mmHg, inH

2

O, ftH

2

O, torr, kg/cm

2

, cmH

2

O, oz/in

2

Display (type, size, update rate)

Ranges up to 1999: 3

1

/

2

digit LCD, 

1

/

2

" digit height

3000 and 5000 psi ranges: 4 digit LCD, 0.4" digit height
3 readings per second nominal display update

Accuracy (linearity, hysteresis, repeatability)

±0.25% of full scale or better, ±1 least significant digit

Output Characteristics

True analog output, 50 millisecond typical response time

Loop Supply Voltage

Any DC supply/loop resistance that maintains 8 to 32
VDC at gauge terminals. Reverse polarity protected.

Low Loop Warning

(below approximately 7.8 VDC)

Ranges up to 1999: Colon appears
3000 and 5000 psi ranges: All decimal points flash

Controls & Location

TEST button sets output to test level, 0-100% range
Internal potentiometers: Loop 4 mA and 20 mA
Ranges up to 1999: Front zero, span & test pots
3000 and 5000 psi ranges: Top zero, span & test pots
All models: Non-interactive zero & span, ±10% range

Temperature Stability (relative to 77°F or 25°C)

±1% FS for offset & span, 32 to 158°F (0 to 70°C) typical
±2% FS for offset & span, 32 to 158°F (0 to 70°C) typical
for 3 and 5 psi ranges

Weight (approximate)

Gauge: 9 ounces, shipping weight: 1 pound

Housing

Extruded aluminum case, light gray epoxy powder coated
Black polycarbonate cover, front and rear gaskets

Pressure/Vacuum Connection & Material

1

/

4

" NPT male, all wetted parts are 316 SS

Overpressure & Burst

5000 psig for 3000 psig range
7500 psig for 5000 psig range
All others 2x rated pressure minimum
Burst: 4x rated pressure minimum or 10,000 psi,
whichever is less

Storage temperature:

–40 to 203°F (–40 to 95°C)

Operating temperature:

–4 to 185°F (–20 to 85°C)

Compensated temperature:

32 to 158°F (0 to 70°C)

1

/

4

" NPT

3.38"

0.75"

PSIG

Span

Zero

1

/

4

" NPT

2.88"

3.38"

0.75"

1.65"

PSIG

Turn at

hex

fitting

only!

Zero

Span

Ranges up to 1999

3000 and 5000 psi ranges

Zero, Test, Span

OMEGA Engineering Inc./Made in USA

OMEGA Engineering Inc./Made in USA

0.75"

3 ft long,
2-conductor,
22 AWG
shielded cable

TEST

Test

TEST

1400

1200

1000

800

600

400

200

0

Max Loop Resistance (Ohms)

8

12

16

20

24

28

32

Loop Supply Voltage (DC)

Voltage Compliance for

4-20 mA Current Loop

Test

Reviews: