background image

indicates  _ _ _ _  with the first underscore blinking, and with 

CFGPC on the lower display. 
Enter the pass code as described in the Pass Code Entry section. 

Restore Factory Configuration

The upper display will be blank, and the lower display will display 

either USER_ or FCTRY.
If USER_ is selected, the existing user configuration will be retained 

and will be accessible for modification in the following steps. To 

select USER_, press and release the 

t

 button. The lower display 

will indicate USER_.
If FCTRY is selected, the existing user configuration will be replaced 

by the configuration as it left the factory and will be accessible for 

modification in the following steps. To select FCTRY, press and 

release the 

s

 button. The lower display will indicate FCTRY.

Press and release the SEL button to move on to the next parameter.

Zero Tare Configuration

The upper display will be blank, and the lower display will indicate 

either ZTARE or NOZTR.
If ZTARE is selected, the user will be able to manually zero the 

gauge from the normal operating mode.
To select ZTARE, press and release the 

s

 button. The lower display 

will indicate ZTARE.
If NOZTR is selected the user will be prevented from zeroing the 

gauge from the normal operating mode. This is default setting for 

absolute reference ranges. 
To select NOZTR, press and release the 

t

 button. The lower display 

will indicate NOZTR.
Press and release the SEL button to move on to the next parameter.

Setpoint Type Configuration

The lower display will either indicate DBAND or ADJ_H.
If DBAND is selected, each output relay will operate with a 1% of 

full-scale deadband between set and reset. 
To select DBAND, press and release the 

s

 button. The lower 

display will indicate DBAND.
If ADJ_H is selected, each output relay will have an adjustable SET 

point and an adjustable RESET point. 
To select ADJ_H, press and release the 

t

 button. The lower display 

will indicate ADJ_H.
Press and release the SEL button to move on to the next parameter.

Alarm Annunciator Function Selection

The lower display will indicate either A_ACK, M_ACK or NO_AN.
If A_ACK is selected, an alarm condition will be automatically 

acknowledged when the alarm condition clears. When an alarm 

condition occurs, the LED for that alarm will begin to blink red and will 

continue to blink red until it has been manually acknowledged or until 

the alarm condition clears. If an alarm is manually acknowledged, the 

LED will be steadily red while the alarm condition continues to exist. 

The LED will be steadily green whenever no alarm condition exists.
If M_ACK is selected, an alarm condition must be manually 

acknowledged. When an alarm condition occurs, the LED for that 

alarm will blink red if the alarm condition exists or green if the alarm 

condition no longer exists. The LED will continue to blink until it has 

been manually acknowledged by a pressing the TEST button. Once 

an alarm has been acknowledged, the LED will be steadily red while 

the alarm condition exists or green when the alarm no longer exists.
If NO_AN is selected, the LEDs will not blink. When an alarm condi-

tion occurs, the LED associated with that alarm will be illuminated 

steadily red if the alarm condition exists or green if the alarm condi-

tion no longer exists. In addition, the LCD display for ALARM1 and 

ALARM2 will not be displayed during alarm conditions.
Use the 

s

 or 

t

 buttons to cycle through the three choices. When 

the lower display indicates the desired annunciator action, press 

and release the SEL button to move on to the next parameter.

Alarm Action Selection (Fixed Deadband Configuration)

The lower display will display either SP1_L or SP1_H.
If SP1_L is selected Alarm 1 will be a low alarm. Alarm 1 will be SET 

when the pressure falls below Setpoint 1. Alarm 1 will be RESET 

when the pressure rises above Setpoint 1 plus the preset deadband. 

To select SP1_L, press and release the 

t

 button. The lower display 

will indicate SP1_L.
If SP1_H is selected Alarm 1 will be a high alarm. Alarm 1 will be 

SET when the pressure rises above Setpoint 1. Alarm 1 will be 

RESET when the pressure falls below Setpoint 1 minus the preset 

deadband. To select SP1_H, press and release the 

s

 button. The 

lower display will indicate SP1_H.
Press and release the SEL button to move to Alarm 2.
The upper display will be blank, and the lower display will display 

either SP2_L or SP2_H.
If SP2_L is selected Alarm 2 will be a low alarm. Alarm 2 will be SET 

“Set Point” is defined as the pressure value that will result in a 

change of state only from a normal to an alarm condition. 
“Trip Point” is defined as the pressure value that will result in a 

change of state of alarm condition, and includes the effect of dead-

band when returning from an alarm to a normal condition.

Set Point 1

From the normal operating mode press the SEL button to display 

Trip Point 1. 
Press and hold the TEST button and press the SEL button. Release 

both buttons when the display indicates  – – – – .
If pass code protection is enabled, before the unit enters the Set 

Point 1 Adjust Mode, the display initially indicates  _ _ _ _  with 

the left-most underscore blinking, and with TSTPC on the display. 
Enter the pass code as described in the Pass Code Entry section. 
While in the Set Point 1 Adjust mode with no buttons pressed, the 

display will indicate Trip Point 1 with TRIP1 blinking at a slow rate 

on the lower display, and the alarm indicators and the retransmis-

sion output will correspond to the applied pressure.
To adjust the Set Point 1 value, press and hold the TEST button. 

The display will indicate Set Point 1 with SP1 on the lower display.
Operate the 

s

 and 

t

 buttons to adjust Set Point 1 to the desired 

value. Release the TEST button to store the Set Point 1 value. 
Note: The gauge will not respond to changes in applied pressure 

while the TEST button is pressed. The alarm relays, LEDs, LCD 

alarm icons, and the DAR output will maintain their prior states until 

the TEST button is released.
To exit the Set Point 1 Adjust mode and return to the normal operat-

ing mode, press and release the SEL button.

Set Point 2

From the normal operating mode press the SEL button twice to 

display Trip Point 2. 
Press and hold the TEST button and press the SEL button. Release 

both buttons when the display indicates  – – – – .
If pass code protection is enabled, before the unit enters the Set 

Point 2 Adjust Mode, the display initially indicates  _ _ _ _  with 

the left-most underscore blinking, and with TSTPC on the display. 
Enter the pass code as described in the Pass Code Entry section.
While in the Set Point 2 Adjust mode with no buttons pressed, the 

display will indicate Trip Point 2 with TRIP2 blinking at a slow rate 

on the lower display, and the alarm indicators and the retransmis-

sion output will correspond to the applied pressure.
To adjust the Set Point 2 value, press and hold the TEST button. 

The display will indicate Set Point 2 with SP2 on the lower display.
Operate the 

s

 and 

t

 buttons to adjust Set Point 2 to the desired 

value. Release the TEST button to store the Set Point 2 value. 
Note: The gauge will not respond to changes in applied pressure 

while the TEST button is pressed. The alarm relays, LEDs, LCD 

alarm icons, and the DAR output will maintain their prior states until 

the TEST button is released.
To exit the Set Point 2 Adjust mode and return to normal operation, 

press and release the SEL button.

From the normal operating mode press the SEL button to display the 

desired trip point (SET_1, RST_1, SET_2, or RST_2).
Press and hold the TEST button and press the SEL button. Release 

both buttons when the display indicates  – – – – .
If pass code protection is enabled, before the unit enters the Set 

Point Adjust Mode, the display initially indicates  _ _ _ _  with the 

left-most underscore blinking, and with TSTPC on the lower display. 
Enter the pass code as described in the Pass Code Entry section. 
While in the Trip Point Adjust mode with no buttons pressed, the 

display will indicate the trip point value with its designator (SET_1, 

RST_1, SET_2, or RST_2) blinking at a slow rate.
To adjust the displayed trip point value, press and hold the TEST 

button. The display will continue to indicate the trip point value.
Operate the 

s

 and 

t

 buttons to adjust the trip point to the desired 

value. The trip point value is stored when the TEST button is 

released. Note: The relays and indicators will not correspond to the 

applied pressure value until the TEST button is released.
To exit the Trip Point Adjust mode and return to the normal operat-

ing mode, press and release the SEL button.

From the normal operating mode, press and hold the TEST and 

the 

s

 buttons. 

Then press the SEL button. 
Release all buttons when the display indicates CFG.
Before the gauge enters the Configuration mode, the display initially 

User Configuration

A pass code is required to calibrate and configure the gauge. 

Additional levels of security may be enabled by defining separate 

pass codes for calibration, user configuration, and output test and 

set point adjust modes. See Changing the User-Defined Pass Code 

at the end of this manual to change pass codes.
Functions in user configuration mode 

  Restore original factory configuration 

  Enable/disable zero tare function 

  Fixed 1% deadband or adjustable hysteresis mode of operation 

  Operation for blinking alarm LEDs 

  Set point modes (high alarm/low alarm or state at power-up) 

  Relay action mode (normal/reverse) 

  DAR model retransmission output upper and lower limits 

  Enable/disable a pass code for output test and set point adjust
When the gauge enters a mode requiring a pass code, the display 

indicates  _ _ _ _  with the first underscore blinking, and either 

TSTPC, CFGPC, CALPC on the lower display. All three pass codes 

are initially set to the factory default of 3510.
Note: During pass code entry the LEDs will be off and the gauge will 

not respond to changes in applied pressure. The relays will maintain 

their prior state. The gauge will automatically revert to the normal 

operation if no buttons are operated for approximately 15 seconds.
Use the 

s

 and 

t

 buttons to set the left-most digit to 3.

Press and release the SEL button to index to the next position. The 

3 will remain, and the second position will be blinking.
Use the 

s

 and 

t

 buttons to select 5.

Press and release the SEL button to index to the next position. 3 5 

will remain, and the third position will be blinking.
Use the 

s

 and 

t

 buttons to select 1.

Press and release the SEL button to index to the next position. 3 5 

1 will remain, and the fourth position will be blinking.
Use the 

s

 and 

t

 buttons to select 0.

Press and release the SEL button to proceed.
If an incorrect pass code was entered, the gauge will to exit to the 

normal operating mode. Upon successful pass code entry, follow 

the steps in the appropriate section of this manual.
Note: To exit a mode at any time, press and hold the SEL button 

until the display indicates  – – – – .

If the gauge is not indicating zero with zero pressure applied but is 

within approximately 3% of full scale pressure of zero, you may tare 

the gauge to zero. This feature may be enabled or disabled. Absolute 

ranges are configured with this feature turned off.
From the normal operating mode with the gauge port open to 

atmosphere, press and hold both the 

s

 and 

t

 buttons and press 

the SEL button. The relay outputs and the retransmission output will 

hold the last value, and the visual indicators will be deactivated. 

Release all buttons when the display indicates o o o o.
The display will indicate a newly calculated zero tare value with 

Z OFF on the lower display. Note: If not within approximately 3% 

of zero, Err0 will be displayed. Press the SEL button to cancel the 

operation and return to normal operating mode without affecting 

any existing zero tare value.
To cancel and remove any existing zero tare value, press and 

release the 

t

 button. The display will indicate zero. To restore the 

newly calculated zero tare value, press and release the 

s

 button.

To exit the Zero/Tare mode, press and release the SEL button. The 

gauge will return to normal operation.

From the normal operating mode, press and hold the TEST button 

and press the SEL button. Release both buttons when the display 

indicates – – – –  or _ _ _ _.
If pass code protection is enabled, the display indicates _ _ _ _  

with the left-most underscore blinking, and TSTPC. 
Enter the pass code as described in the Pass Code Entry section. 
While in the Test mode with no buttons pressed, the display will indi-

cate the pressure with the engineering units blinking at a slow rate.
When the TEST button is pressed, the LED indicators and the relays 

will toggle to their opposite states. The display will indicate the 

preset test value with TEST on the lower display, and the retrans-

mission output on DAR models will correspond to the test value. 
Pressing the 

s

 or the 

t

 button while holding the TEST button will 

raise or lower the test value. Note that the gauge will not respond to 

changes in applied pressure while the TEST button is held.
When the TEST button is released, the display, the LED indicators, 

and the relay outputs will correspond to the applied pressure.
Press and release the SEL button to exit the Output Test mode and return 

to normal operation.

Zero Tare Mode

Pass Code Entry

Adjust Setpoint, Fixed Deadband Mode

User Configuration—cont.

Output Test Mode

Adjust Trip Point, Adjustable Hysteresis Mode

DPG1000DAR Series Digital Pressure Gauges Alarms and 4-20 mA Output

3

Reviews: