background image

The gauge is powered on whenever a supply voltage is applied. 

Warm-up time is negligible. The gauge may be left on at all times. 

All configuration information is stored in non-volatile memory. 
When power is first applied, the gauge proceeds through a startup 

sequence. During the startup sequence, relays are de-energized, 

the status LEDs are off, and the retransmission output is low (0 mA).
1. The firmware version number is displayed briefly
2. All active display segments are turned on for approx. 1 second.
3. The full scale pressure is indicated for approx. 1 second while the 

engineering units and FS (full scale) are indicated for 1/2 second 

on the character display.

4. The display is tested again for approximately 1 second.
The gauge then proceeds to the normal operating mode. 
For DAR models the retransmission output corresponds to the 

applied pressure.

The factory default configuration is 1% fixed deadband mode, zero 

tare enabled, and no pass code required for test function.
Alarms may be configured to operate in fixed deadband mode or 

adjustable hysteresis mode. 
In the fixed deadband mode, the alarm set/reset point deadband is 

factory set to 1% of full-scale. Each alarm may be configured as 

either HI or LO with a user adjustable alarm set point for each relay.
In the adjustable hysteresis mode, two independent set and reset 

trip points are user adjustable for each relay. The set or reset state 

at power up when between trip points is user configurable.

Each relay may be independently configured as a high or low alarm 

in User Set-up and operate as shown in the table below.

The relevant LCD alarm icon will indicate an alarm condition.
The relevant bi-color LED will be illuminated green for a normal 

condition or red for an alarm condition.
The LED will blink at a slow rate until the alarm is acknowledged 

unless the annunciator mode was disabled in set-up. 
Alarms may be configured to be automatically acknowledged when 

the alarm condition clears or configured to be manually acknowl-

edged by pressing the TEST button.
The applied pressure, the value of Trip Point 1, and the value of Trip 

Point 2 may be selected for display as follows:
When the applied pressure is being displayed, press and release 

the SEL button. The Trip Point 1 value will be displayed with TRIP1 

on the lower display.
When the Trip Point 1 value is being displayed, press and release 

the SEL button. The upper display will indicate the Trip Point 2 value 

with TRIP2 on the lower display.
When the Trip Point 2 value is being displayed, press and release 

the SEL button. The upper display will indicate the applied pressure 

with engineering units on the lower display.

4

  Read these instructions before using the gauge. Configuration may 

be easier before installation. Contact the factory for assistance.

4

  These products do not contain user-serviceable parts. Contact us 

for repairs, service, or refurbishment.

4

  Gauges must be operated within specified ambient temperature ranges.

4

  Outdoor or wash down applications require a NEMA 4X gauge or 

installation in a NEMA 4X housing.

4

  Use a pressure or vacuum range appropriate for the application.

4

  Use fittings appropriate for the pressure range of the gauge. 

4

  Due to the hardness of 316 stainless steel, it is recommended that 

a thread sealant be used to ensure leak-free operation.

4

 For contaminated media use an appropriate screen or filter to 

keep debris out of gauge port. 

4

  Remove system pressures before removing or installing gauge.

4

  Install or remove gauge using a wrench on the hex fitting only. Do 

not attempt to turn gauge by forcing the housing. 

4

  Do not exceed relay current and voltage ratings. Use an appropri-

ate contactor for larger loads. Inductive inrush currents may be up 

to 5x normal current and may require an RC snubber. 

4

 Good design practice dictates that positive displacement liquid 

pumps include protection devices to prevent sensor damage from 

pressure spikes, acceleration head, and vacuum extremes.

 

Avoid permanent sensor damage! Do not apply vacuum to non-

vacuum gauges or hydraulic vacuum to any gauges. 

 

Avoid permanent sensor damage! NEVER insert objects into 

gauge port or blow out with compressed air.

 Gauges are not for oxygen service. Accidental rupture of sensor dia-

phragm may cause silicone oil inside sensor to react with oxygen.

 NEVER connect the gauge wires directly to 115 VAC or perma-

nent damage will result.

Gauge reference models read zero with the gauge port open. 
Compound ranges read vacuum in inches of Mercury, pressure in 

psig, and zero with the gauge port open.
1000 psi and higher sensors are a sealed reference type. They read 

zero with the gauge port open are internally referenced to 14.7 psi. 

They are functionally similar to gauge reference sensors.
Absolute reference gauges read zero at full vacuum and atmo-

spheric pressure with the gauge port open. Note that readings of 

atmospheric pressure vary continuously. 

The DAR 4-conductor cable with the RED and BLACK leads is for 

the gauge power supply. 

Connect to 8-24 VAC, 50/60Hz or 9-32 VDC. The gauge will operate 

on either AC or DC power and there is no need to observe polarity. 

An unregulated power supply can be used. Note that standard 24 

VAC transformers with small loads may operate at voltages over the 

24 VAC limit. The supply voltage, when within the stated ranges, 

has negligible effect on the gauge calibration. Operation below 9 

VDC or 8 VAC may cause erratic or erroneous readings or output.
When operating multiple gauges from the same power supply, refer 

to the mA rating in the specifications to ensure adequate power. 

Route the wires away from heat sources and moving equipment.

The alarm contacts are rated at 1A/24VDC or 0.5A/115VAC. Using 

mechanical relay contacts above their rating, or with large inductive 

loads, will shorten their life. For inductive loads, RC snubbers or arc 

suppression devices are required to protect the contacts. For large 

loads a higher capacity contactor is required. 
No internal fusing is included in the alarm contact circuits. The 

alarm outputs should be externally fused by the user in applications 

where good design practice dictates.

Types of Gauges

In the adjustable hysteresis mode, two independent set and reset 

trip points used for each relay and operate as shown below.

The LEDs indicate green for a RESET state and red for a SET state. 

Refer to the table for output states as a function of applied pressure.
If the gauge is configured for alarms, ALARM1 and ALARM2 will be 

indicated when alarm conditions exist, and the associated LEDs will 

blink to indicate unacknowledged alarm conditions. 
Alarms may be configured to be automatically acknowledged when 

the alarm condition clears or configured to be manually acknowl-

edged by pressing the TEST button.
The applied pressure, the SET trip points, and the RESET trip points 

may be selected for display as follows.
While the applied pressure is being displayed, press and release the 

SEL button. The upper display will indicate the value of set point 1 

with ‘SET_1’ on the lower display.
While set point 1 is being displayed, press and release the SEL but-

ton. The upper display will indicate the value of reset point 1 with 

‘RST_1’ on the lower display.
While reset point 1 is being displayed, press and release the SEL 

button. The upper display will indicate the value of set point 2 with 

‘SET_2’ on the lower display.
While set point 2 is being displayed, press and release the SEL but-

ton. The upper display will indicate the value of reset point 2 with 

‘RST_2’ on the lower display.
While the reset point 2 is being displayed, press and release the 

SEL button. The upper display will indicate the applied pressure 

and engineering units.

DAR models have a 4-20 mA retransmission output that corre-

sponds to the applied pressure, except when in zero/tare mode, 

test mode, or during setup. Characteristics of the output types are 

listed below. 

See specifications for output resolution. Note that analog output 

resolution is always over the entire sensor range and is updated 

approximately 16 times per second. 
The 4-20 mA output provides power to the current loop and output 

drive is determined by power source.

Operation with Fixed Deadband Alarms

Contact Rating and Protection

Power 

Up

Operation with Adjustable Hysteresis Alarms

Alarm Types

Sensor

Full vacuum

“0” on 

display

Full  

pressure

Gauge ref. pressure

n/a

4 mA

20 mA

Gauge ref. vacuum

20 mA

4 mA

n/a

Absolute reference

4 mA

4 mA

20 mA

Normal (Fail-safe) acting, RESET value less than SET

Pressure

< Low 

RESET

 point

> High 

SET

 point

Relay coil

On

Off

Alarm 1 continuity

C-NO (Red-White)

C-NC (Red-Black)

Alarm 2 continuity

C-NO (Brown-Blue)

C-NC (Brown-Green)

LED

Green

Red

Normal (Fail-safe) acting, SET value less than RESET

Pressure

< Low 

SET

 point

> High 

RESET

 point

Relay coil

Off

On

Alarm 1 continuity

C-NC (Red-Black)

C-NO (Red-White)

Alarm 2 continuity

C-NC (Brown-Green)

C-NO (Brown-Blue)

LED

Red

Green

Reverse acting, RESET value less than SET

Pressure

< Low 

RESET

 point

> High 

SET

 point

Relay coil

Off

On

Alarm 1 continuity

C-NC (Red-Black)

C-NO (Red-White)

Alarm 2 continuity

C-NC (Brown-Green)

C-NO (Brown-Blue)

LED

Green

Red

Reverse acting, SET value less than RESET

Pressure

< Low 

SET

 point

> High 

RESET

 point

Relay coil

On

Off

Alarm 1 continuity

C-NO (Red-White)

C-NC (Red-Black)

Alarm 2 continuity

C-NO (Brown-Blue)

C-NC (Brown-Green)

LED

Red

Green

Power-up relay state when between SET and RESET

Config. set to SP_L

RESET

Config. set to SP_H

SET

DAR Output Types

Electrical Connections

Installation Precautions

Alarm Contact 

Ratings

0.5A/115VAC, 

1A/24VDC,  

non-inductive

6-conductor relay wires

BLACK NC Normally Closed

SPDT 

1

RED

C Common
NO Normally Open

GREEN

NC Normally Closed

SPDT 

2

BROWN

C Common

BLUE

NO Normally Open

Power wires

BLACK

8-24 VAC 50/60 Hz or  

9-32 VDC

RED

Analog output wires

+ Output

GREEN

– Output

NC 1 

C 1 

NO 1

NC 2 

C 2 

NO 2

DAR Output

Green is com-

mon with Black

DPG1000DAR Series Digital Pressure Gauges with Alarms and 4-20 mA Output

2

Normal acting, High alarm SP_H

Pressure

< Set point – 1%FS

> Set point

Relay coil

On

Off

Alarm 1 continuity

C-NO (Red-White)

C-NC (Red-Black)

Alarm 2 continuity

C-NO (Brown-Blue)

C-NC (Brown-Green)

LED

Green

Red

Normal acting, Low alarm SP_L

Pressure

< Set point

> Set point + 1%FS

Relay coil

Off

On

Alarm 1 continuity

C-NC (Red-Black)

C-NO (Red-White)

Alarm 2 continuity

C-NC (Brown-Green)

C-NO (Brown-Blue)

LED

Red

Green

Reverse acting, High alarm SP_H

Pressure

< Set point – 1%FS

> Set point

Relay coil

Off

On

Alarm 1 continuity

C-NC (Red-Black)

C-NO (Red-White)

Alarm 2 continuity

C-NC (Brown-Green)

C-NO (Brown-Blue)

LED

Green

Red

Reverse acting, Low alarm SP_L

Pressure

< Set point

> Set point + 1%FS

Relay coil

On

Off

Alarm 1 continuity

C-NO (Red-White)

C-NC (Red-Black)

Alarm 2 continuity

C-NO (Brown-Blue)

C-NC (Brown-Green)

LED

Red

Green

Reviews: