10. Regulations

This instrument conforms to the actual CE regulations. For a copy of the ‘CE declaration 

of conformity’ see section 3. Applicable regulations are :
Security regulations EN-61010-1 (‘Fixed’ equipment, ‘Permanently connected’. 

‘Double’ isolation. ‘CAT-II’ category)
Electromagnetic compatibility regulations EN-61326-1

According  to  directive  2012/19/EU,  electronic  equipment  must  be  re-

cycled in a selective and controlled way at the end of its useful life.

This instrument does not provide a general mains switch  and will start operation as 

son as power is connected. The instrument does not provide protection fuse, and the 

fuse must be added during installation.

Risk of electrical shock. Instrument terminals can be connected to 

dangerous voltage.

Instrument protected with double isolation. No earth connection 

required.

Instrument conforms to CE rules and regulations. 

Range, scaling and decimal point 

0/600 Vac = 0/600

Alarm 1 

as maximum

   Setpoint 

1000

   Hysteresis 

0 counts

Alarm 2 

as maximum

   Setpoint 

1000

   Hysteresis 

0 counts

External control 

off

Fast access 

all off

Tools

   Option 1 

off 

(retains last configuration value)

   Step 

1

   Average 

0

   Manual offset 

0

   Second scaling 

0/600

   ‘Eco’ mode 

off

   Temperature resolution 

   Degrees 

ºC

   Alpha 

385

   cJc 

on

   AC ‘deadband’ 

20

   Luminosity 

3

   Password 

off

Option

   Analog output 

0/100.0=4/20 mA

   Serial Modbus RTU 

9600 bps, address 1, format 8n1

Jumpers ‘S’ 

range for 600 Vac

Jumper ‘T’ 

external contact ‘EK’ function

11. Factory configuration

9. Configuration menu

Press ‘SQ’ (

<

for 1 second to access  

the ‘Configuration menu’.

Input

AC signals

600 V

200 Vac

20 Vac

2 Vac

200 mVac

60 mVac

5 Aac

20 mAac

DC signals

±600 Vdc

±200 Vdc

±20 Vdc

±2 Vdc

±200 mVdc

±60 mVdc

±5 Adc

±20 mAdc

Process

4/20 mA 

0/10 Vdc

Thermocouples

thermocouple K

thermocouple J

thermocouple E

thermocouple N

thermocouple L

thermocouple R

thermocouple S

thermocouple B

thermocouple T

thermocouple C

NTC probes

Resistances

0 to 5 K

0 to 50 K

Alarm 1

Setpoint

Hysteresis

Type

Alarm 2

Setpoint

Hysteresis

Type

Temp.  

resolution.

1º resolution

0.1º resolution

Scaling 2

Decimal

Display Low

Display High

‘Eco’ mode

5 to 255 sec.

Filter

0 a 100

Steps

Offset

Decimal 1

Decimal 2

Decimal 0

Scaling 2

Decimal 3

Option 1

analog

relay

None

Tools

Modbus RTU

enters 

the 

analog  output 

c a l i b r a t i o n 

menu

Scaling

Decimal

Display Low

Display High

Key UP

Maximum

Minimum

Setpoint 1

Setpoint 2

Minimum

Hold

Maximum

External 

control

Disabled

Alpha

Alpha 385

Alpha 390

Front keypad menu operation
Key SQ
 (

<

) -   1. Press to access the ‘Configuration menu’.  

 

2. Press to enter into the actual menu entry. 

 

3. Press to accept a value.

Key UP (

5

) -   1. Press to access the ‘Fast access’ menu.  

 

2. Press to move through available menu options. 

 

3. Press to increase the value of a numerical parameter.

Key LE (

3

) -   1. Without function.  

2. Press to return to a previous level of the menu, discarding changes (to 

validate changes, use SQ (

<

)).  

3. Move through the digits of a numerical parameter.

To save the configuration changes, press key LE (

3

) until exiting the menu (shown by 

flashing decimal points). Instrument shows the signal range selected and starts opera-

tion with the new configuration.

PTC probes

KTY 121

KTY 210 and 220

Minimum

Brightness

Maximum

Standard

Password

Version

Factory reset

‘AC deadband’

‘Deadband’ on AC 

ranges. Value 0 to 100.

Option

 

1  

configuration

Analog

Display Low

Display High

Modbus RTU

Address

Speed

1 to 247

9600 bps

4800 bps

Format

Cold junction

Thermocouple cold junction 

compensation ‘on’ or ‘off’

Degrees

Celsius

Fahrenheit

RTD probes

Pt100 (2 wires)

Pt500

Pt1000

Ni100

Ni200

Ni1000

Pt100 (3 wires)

Potentiometer

If you need additional information, see section 3 to download 

the full User’s Manual.

12. User’s manual

!

www.omega.com/ DP20.html

600U

600U

tArE

Tare function

Frequency

FrEq

Note: The AC powered units cannot be shipped to Canada.