 M2113/1294

INSTRUCTION

SHEET

DP18 Series

Model DP18-P9
Differential Process Indicator

CCD1294APC1B

1

10

D
C
B
A

+

-

REAR VIEW

Setpoint R1
(option)

Setpoint R2
(option)

FRONT VIEW

FIG. 2

FIG. 1

SIGNAL
INPUT

SPAN : ADJUST THE MAXIMUM READING.
OFFSET : NOT IN SERVICE

SPAN ADJUSTMENT IS ACCESSIBLE BEHIND THE LOW DOOR.

Isolated digital output

(option)

HOLD,

 latch the reading

display, while these pins
are linked

ANALOG OUTPUT
(OPTION)

POWER SUPPLY

see instrument label

DISPLAYS . . . . . . . . . . . . . . . . . . . . . .  3      digits, 7 segment, red LED
HEIGHT . . . . . . . . . . . . . . . . . . . . . . . .  0.56" (14.2 mm.)
SYMBOLS . . . . . . . . . . . . . . . . . . . . . .  ± 1.8.8.8
DECIMAL POINTS . . . . . . . . . . . . . . . .  Selectable by jumpers
OVERRANGE INDICATION . . . . . . . . .  Display flashes 1999

INPUT CONFIGURATION . . . . . . . . . . .  Bipolar single
ZERO . . . . . . . . . . . . . . . . . . . . . . . . .  Automatic
SPAN ADJUSTMENT . . . . . . . . . . . . . .  ± 5 %

CONVERTER . . . . . . . . . . . . . . . . . . . .  Dual-slope, average value
POLARITY . . . . . . . . . . . . . . . . . . . . . .  Automatic  ±
SIGNAL INTEGRATION PERIOD . . . . .  80 ms.
READ RATE . . . . . . . . . . . . . . . . . . . .  3.12 / sec.
HOLD . . . . . . . . . . . . . . . . . . . . . . . . .  Optional

NOISE REJECTION NMR . . . . . . . . . . .  50 dB. 50/60 Hz.
ACCURACY . . . . . . . . . . . . . . . . . . . .  0.15 %   ± 1 count
WARMUP TO RATED ACCURACY .  .  .  2  minutes
SPAN TEMPCO . . . . . . . . . . . . . . . . . .  100 ppm.
ZERO TEMPCO . . . . . . . . . . . . . . . . . .  2.5 µV/°C.

OPERATING TEMPERATURE . . . . . . .  0 to 50 °C (32 to 122 °F)
STORAGE TEMPERATURE . . . . . . . . .  -40 to 80 °C (-40 to 176 °F)
WEIGHT . . . . . . . . . . . . . . . . . . . . . . . .  310 gr. (0.68 lb)
CASE MATERIAL . . . . . . . . . . . . . . . .  ABS, DIN 43700, black color
STANDARD POWER . . . . . . . . . . . . . .  115 Vac. ± 10 %, 50/60 Hz.
POWER CONSUMPTION . . . . . . . . . . .  5.5 VA for AC.
ELECTRICAL CONNECTIONS . . . . . . .  Push-in cable connectors
BURN-IN . . . . . . . . . . . . . . . . . . . . . . .  24 h.

½

SPECIFICATIONS

SPAN

OFFSET

FIG. 3

A

B

C

SPAN ADJUST

ZERO ADJUST

B

A

SIGNAL CONDITIONER         COMPONENTS VIEW

THIS SIGNAL CONDITIONER INPUT ALLOWS THE DISPLAY IN ENGINEERING UNITS OR PERCENTAGES, THE DIFFERENCE BETWEEN TWO
PROCESS SIGNALS OF 0-20 mA OR 4-20 mA.

SIGNAL INPUT  "A"  MUST CORRESPOND, THEORETICALLY TO THE HIGHER SIGNAL,IN ORDER THAT THE DISPLAY READING BE POSITIVE.
IF THE SIGNAL "B" IS HIGHER THAN  "A", THE DISPLAY READING WILL BE NEGATIVE.

CLOSE THE APPROPRIATE DECIMAL POINT JUMPER (FIG.5), CORRESPONDING TO THE RANGE SELECTED.

INSTRUMENT TO READ THE DIFFERENCE BETWEEN TWO PROCESS SIGNALS AND DISPLAY IN
ENGINEERING UNITS.
SIGNALS CAN BE : 0-20 mA. or 4-20 mA.

Signal low

Signal low

Signal high

Signal high

out

out

TRANSDUCER "A"

TRANSDUCER "B"