Range Selection
Rotary switches and a slide switches on the side of the module are
used to select input and output ranges to match your application.
Switch A: Excitation voltage
Switch B: Input range
Switch C: Input offset (see table on next page)
Switch D: Output range
Switch E : Set to "V" for voltage output or
Set to "I" for current output
It is generally easier to select ranges before installing the module
on the DIN rail. The tables below list available settings, ranges,
and offsets. The module side label lists common ranges.
Determine how much output in millivolts the load cell will pro-
duce at full load. Multiply the manufacturer's mV/V sensitivity
specification by the applied excitation voltage.
For example, a load cell rated for 3 mV/V sensitivity using 10
VDC excitation will produce an output of 0 to 30 mV for load
variations from 0 to 100%.
3 mV/V sensitivity X 10 VDC excitation = 30 mV range
Excitation Voltage Setup
Refer to the sensor manufac-
turer's recommendations to
determine what excitation volt-
age to use.
Set Excitation rotary switch A to
desired excitation voltage.
After installation the excitation
fine adjust potentiometer may
be used to precisely trim this
voltage, if desired.
I/O Range Selection B, C, D, E
1. From the table below, find the rotary switch combination that
matches your I/O ranges and set rotary switches B, C, and D.
2. Set switch E to "V" for voltage output or "I" for current output.
3. For ranges that fall between the listed ranges use the next
highest setting and trim the output signal with the zero and
span potentiometers as described in the Calibration section.
Using Offset Switch C
Offset switch C allows canceling or taring of non-zero dead-
weights or other sensor offsets such as:
O
Compensate for tare weights or scale deadweight to get
zero output when a load is on the platform.
O
Compensate for low-output sensors (e.g., less than 1 mV/V)
that may have large zero offsets. Switch C can realign the
zero control so it has enough range to produce the desired
zero output.
O
Raising the offset to allow calibration of bipolar sensors
such as ±10 mV.
O
Lowering the offset to compensate for elevated input
ranges such as 10-20 mV.
1. Switch C does not interact with
any other switch and is the
only switch needed to correct
zero offsets. Its only purpose
is to adjust or cancel effects of
the low end of the input range
not corresponding nominally
to 0 mV. Setting this switch to
“0” results in no offset.
2. To RAISE the output zero, rotate
switch C from “1” thru “7”,
until the Zero control can be set
for your application.
3. To LOWER the output zero,
rotate switch C from “9” thru
“F”, until the Zero control can
be set for your application.
4. After all switches are set,
repeat the calibration proce-
dure.
DMD4059 Series Strain Gauge to DC Isolated Transmitter
2
Output
0-1 V
0-2 V
0-4 V
1-5 V
0-5 V
0-8 V
2-10 V
0-10 V
±5 V
±10 V 0-2 mA 0-4 mA 0-8 mA 2-10 mA 0-10 mA 0-16 mA 4-20 mA 0-20 mA
Switches
BCDE
BCDE
BCDE
BCDE
BCDE
BCDE
BCDE
BCDE
BCDE
BCDE
BCDE
BCDE
BCDE
BCDE
BCDE
BCDE
BCDE
BCDE
Input
0-5 mV
200V
208V
201V
206V
209V
202V
207V
203V
204V
205V
200I
208I
201I
206I
209I
202I
207I
203I
0-10 mV
A00V
A08V
A01V
A06V
A09V
A02V
A07V
A03V
A04V
A05V
A00I
A08I
A01I
A06I
A09I
A02I
A07I
A03I
0-20 mV
300V
308V
301V
306V
309V
302V
307V
303V
304V
305V
300I
308I
301I
306I
309I
302I
307I
303I
0-25 mV
600V
608V
601V
606V
609V
602V
607V
603V
604V
605V
600I
608I
601I
606I
609I
602I
607I
603I
0-30 mV
E00V
E08V
E01V
E06V
E09V
E02V
E07V
E03V
E04V
E05V
E00I
E08I
E01I
E06I
E09I
E02I
E07I
E03I
0-40 mV
B00V
B08V
B01V
B06V
B09V
B02V
B07V
B03V
B04V
B05V
B00I
B08I
B01I
B06I
B09I
B02I
B07I
B03I
0-50 mV
000V
008V
001V
006V
009V
002V
007V
003V
004V
005V
000I
008I
001I
006I
009I
002I
007I
003I
0-100 mV
800V
808V
801V
806V
809V
802V
807V
803V
804V
805V
800I
808I
801I
806I
809I
802I
807I
803I
0-120 mV
F00V
F08V
F01V
F06V
F09V
F02V
F07V
F03V
F04V
F05V
F00I
F08I
F01I
F06I
F09I
F02I
F07I
F03I
0-200 mV
100V
108V
101V
106V
109V
102V
107V
103V
104V
105V
100I
108I
101I
106I
109I
102I
107I
103I
0-250 mV
400V
408V
401V
406V
409V
402V
407V
403V
404V
405V
400I
408I
401I
406I
409I
402I
407I
403I
0-300 mV
C00V
C08V
C01V
C06V
C09V
C02V
C07V
C03V
C04V
C05V
C00I
C08I
C01I
C06I
C09I
C02I
C07I
C03I
0-400 mV
900V
908V
901V
906V
909V
902V
907V
903V
904V
905V
900I
908I
901I
906I
909I
902I
907I
903I
Excitation
Switch A
10 V
A
9 V
9
8 V
8
7 V
7
6 V
6
5 V
5
4 V
4
3 V
3
2 V
2
1 V
1
0 V
0
Offset
% of Span
Switch C
105%
7
90%
6
75%
5
60%
4
45%
3
30%
2
15%
1
0%
0
–15%
9
–30%
A
–45%
B
–60%
C
–75%
D
–90%
E
–105%
F
A
B
C
D
E
0-5 mV0-10 mV0-20 mV0-25 mV0-30 mV0-40 mV0-50 mV0-100 mV
0-200 mV
0-250 mV
BCD
200
209
206
204
203
205
207
Rotary Switches
0-1V
0-5V
1-5V
+/-5V
0-10V
+/-10V
4-20mA
BCD
300
309
306
304
303
305
307
BCD
600
609
606
604
603
605
607
BCD
E00
E09
E06
E04
E03
E05
E07
BCD
B00
B09
B06
B04
B03
B05
B07
BCD
000
009
006
004
003
005
007
BCD
800
809
806
804
803
805
807
BCD
100
109
106
104
103
105
107
BCD
400
409
406
404
403
405
407
BCD
A00
A09
A06
A04
A03
A05
A07
OUTPUT
INPUT
0-30mV IN, 4-20mA OUT: CODE 0E7
Set switch “B” to 0; “C” to E; “D” to 7
EXAMPLE
:
Excitation Switch
Voltage
Position
10V
9V
8V
7V
6V
5V
4V
3V
2V
1V
0V
A
9
8
7
6
5
4
3
2
1
0
1. Set Switch A for desired Excitation Voltage.
2. Set Switches B/C/D for desired Input / Output ranges.
3. Set Switch E for Voltage or Current as required.
4. Set Excitation / Zero / Span / Test Cal. Controls
Connections
3
4
6
9
10
11
12
13
16
Term. #
Signal
Sig. Out –
Sig. Out +
Sense Lead
Sig. Input +
Exc. –
Sig. Input –
Exc. +
Power +
Power –
DMD4059
Strain Gauge to
DC Isolated Transmitter
Output
V I
Excitation
Input
Output
Offset
For more Details
and Instructions
see Data Sheet
4
C
0
8
E
2
A
6
3
F
B
7
5
9
D
1
0
5
1
6
4
9
7 8
3
2
4
C
0
8
E
2
A
6
3
F
B
7
5
9
D
1
4
C
0
8
E
2
A
6
3
F
B
7
5
9
D
1
Electrical Connections
Check white model/serial number label for module operating
voltage to make sure it matches available power.
WARNING! All wiring must be performed by a qualified electri-
cian or instrumentation engineer. See diagram at right for
terminal designations and wiring examples.
Avoid shock hazards! Turn signal input, output, and power off
before connecting or disconnecting wiring. Connect I/O wiring
before power wiring.
Module Power Terminals
When using DC power, either polarity is acceptable, but for
consistency with similar products, positive (+) can be wired to
terminal 13 and negative (–) can be wired to terminal 16.
Signal Input Terminals
Connect up to 4 strain gauges or load cells. See manufacturer’s
specifications for wiring designations and wire color-coding.
Polarity must be observed when connecting inputs.
CAUTION: Never short the excitation leads together. This will
cause internal damage to the module.
Some bridges may have one or two sense leads. See manu-
facturer’s specifications. Sense leads allow the DMD4059 to
compensate for leadwire resistance effects. Observe polarity
when connecting sense leads.
If no sense lead is used, jumper sense (+) terminal 6 and excita-
tion (+) 12.
Calibration should be done after all connections are made.
Signal Output Terminals
Polarity must be observed when connecting the signal output.
The DMD4059 output can be wired to provide either a sinking
or sourcing mA output. If your device accepts a current input,
determine if it provides power to the current loop or if it must be
powered by the DMD4059 module.
Use a multi-meter to check for voltage at your device’s input
terminals. Typical voltage may be 9-24 VDC. See the wiring
diagram for the appropriate connections.