background image

DMD1080 

DMD1080-DC 

DC Input Alarm Trips  

M-5245/0818

DC Input Ranges

24 field selectable ranges via switch settings 
See chart on next page
Voltage: 

0-50 mVDC to 0-10 VDC 

Bipolar Voltage:  ±5 VDC or ±10 VDC 
Current: 

0-1 mADC to 0-20 mADC, 4-20 mADC

Input Impedance and Burden

Voltage: 

250 k

 minimum 

Current: 50 

 typical 

Voltage burden:  1 VDC at 20 mA current input

Isolation

Power to input isolation: 

1200 V  

Common mode protection:  600 VAC

p

 or 600 VDC

Input Loop Power Supply

15 VDC ±10%, regulated, 25 mADC, max. ripple, <10 mV

RMS

May be selectively wired for sinking or sourcing mA input

LoopTracker

Variable brightness LED indicates input loop level and status

Relay Output

Single setpoint dual DPST contact sets, field configurable 
2 Form A (NO) and 2 Form B (NC) contact sets (8 terminals) 
May be field wired for Form C operation

Relay Contact Ratings

8 A @ 240 VAC resistive load 
5 A @ 240 VAC inductive load (cos 

= 0.4) 

8 A @ 30 VDC resistive load 
3.5 A @ 30 VDC inductive load (L/R = 7ms)
See diagram on other side
External contact protection such as an RC snubber is recom-
mended for inductive loads

Setpoint

12 turn potentiometer adjustable from 0 to 100% of span

Deadband

12 turn potentiometer adjustable from 1 to 100% of span 

Output Test/Reset Button

Toggles relay to opposite state when pressed 
Resets latching relay if latching relay mode is selected

Response Time

70 milliseconds typical

Ambient Temperature Range and Stability

–10°C to +60°C operating ambient
Better than 1% of span over operating temperature range
Better than 0.02% of span per °C

Power

85-265 VAC, 50/60 Hz or 60-300 VDC, 2 W maximum 
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 2 W maximum

Housing and Connectors

IP 40, requires installation in panel or enclosure 
For use in Pollution Degree 2 Environment 
Mount vertically to a 35 mm DIN rail 
Four 4-terminal removable connectors, 14 AWG max wire size

Description

The DMD1080 accepts a DC voltage or current input and provide 
visual alarm indication and alarm relay contact outputs. 15 
voltage and 9 current input ranges can be field-configured via 
external rotary and slide switches. Offset ranges such as 1-5 
VDC and 4-20 mADC are also included. 
Heavy-duty relay contacts allow the module to directly control 
high capacity loads. Front-accessible potentiometers are used 
to adjust the alarm setpoint from 0 to 100% and the deadband 
from 1 to 100%.
The DMD1080 provides a single setpoint adjustment of the two 
DPST relay contacts. The alarm output can be field configured 
for HI or LO operation, latching or non-latching, and normal or 
reverse acting. Deadband control can be adjusted from 1 to 
100% and the alarm setpoint from 0 to 100%. 

Sink/Source Input and Loop Supply

For maximum versatility, a current input can be selectively wired 
for sinking or sourcing. This allows the DMD1080 to work with 
powered or unpowered mA inputs. A regulated 15 VDC loop 
excitation supply can be used to power passive input devices 
eliminating the need for an additional DC loop supply. 

Input and Alarm Status LEDs

The input LED varies in intensity with changes in the process 
input signal. A red/green bi-color alarm status LED visually 
indicate alarm status. These LEDs provide a quick visual status 
of your process at all times. 

Output Test / Unlatch

A functional test button can be used to verify the alarm and 
system operation and also provides the additional function of 
unlatching the alarm when the latching mode has been selected.
The output test button greatly aids in saving time during initial 
startup and/or troubleshooting.

Switching Current (A)

Switching Voltage (V)

3  5  10 

30 50 100  300 500

8

5

3

1

0.5
0.3

0.1

AC inductive load 

(cos 

f

 = 0.4)

AC resistive 

load

DC inductive load 

(L/R = 7 ms)

DC resistive 

load

Relay Contact Ratings

Model

Module Power

DMD1080

85-265 VAC, 50/60 Hz or 60-300 VDC

DMD1080-DC

9-30 VDC or 10-32 VAC

e-mail: [email protected] 

For latest product manuals: 

www.omegamanual.info

Shop online at 

omega.com

User’s Guide

Lifetime

TM

MADE IN

WARNING:

 This product can expose you to chemicals includ-

ing nickel, which are known to the State of California to cause 

cancer or birth defects or other reproductive harm. For more 

information go to www.P65Warnings.ca.gov

Reviews: