background image

DMD1080, DMD1080-DC DC Input Alarm Trips

3

Spring Clip

Upper Mount

Lower Mount

Mounting to a DIN Rail

Install module vertically on a 35 mm DIN rail in a protective 
enclosure away from heat sources. 
Do not block air flow. Allow 1” (25 mm) above and below hous-
ing vents for air circulation.

Precautions

WARNING! Avoid shock hazards! Turn signal input, output, and 
power off before connecting or disconnecting wiring, or remov-
ing or installing module. 

Installation

1.  Tilt front of module downward and position the lower mounts 

and spring clips against the bottom edge of DIN rail.

2.  Clip Lower Mount to bottom edge of DIN rail. 
3.  Push front of module upward until upper mount snaps into 

place.

Removal

1.  Push up on bottom back of module.
2.  Tilt front of module downward to release upper mount from 

top edge of DIN rail. 

3.The module can now be removed from the DIN rail. 

Setup and Calibration

The input ranges are factory calibrated and do not require 
adjustment.
The Setpoint potentiometer allows the operator to adjust the 
level at which the alarm is activated. This control is adjustable 
from 0 to 100% of the input range.
The Deadband potentiometer allows the alarm trip and reset 
window to be adjusted symmetrically about the setpoint from 1 
to 100% of the span. This allows the operator to fine tune the 
point at which the alarm trips and resets. 
The deadband is typically used to prevent chattering of the 
relays or false trips when the process signal is unstable or 
changes rapidly.
To calibrate the alarm section, set the deadband control to the 
minimum (counterclockwise). 
Set the signal source to a reference that represents the desired 
trip point. 
Adjust the setpoint control to the point at which the relay chang-
es state form a non-alarm to an alarm condition. The deadband 
will be 1.0% of span in this case. 
If a larger amount of deadband is desired turn the deadband 
potentiometer clockwise. The deadband is symmetrical about 
the setpoint; both transition points will change as deadband is 
increased. 

Output Test Function

When the test button is depressed it will drive the relays to their 
opposite state. This can be used as a diagnostic aid during initial 
start-up or troubleshooting. When released, the relays will return 
to their prior states.

Operation

The green input LED provides a visual indication that a signal 
is being sensed by the input circuitry of the module. It also 
indicates the input signal strength by changing in intensity as 
the process changes from minimum to maximum.
If the LED fails to illuminate, or fails to change in intensity as 
the process changes, check the module power or signal input 
wiring. Note that it may be difficult to see the LEDs under bright 
lighting conditions.
The bi-color alarm LED provides a visual indication of the alarm 
status. In all configurations, a green LED indicates a non-alarm 
condition and a red LED indicates an alarm condition.
In the normal mode of operation, the relay coil is energized in 
a non-alarm condition and de-energized in an alarm condition. 
This will create an alarm condition if the module loses power.
For a normal acting, non-latching configuration, the alarm will 
activate when the input signal exceeds the setpoint (HI alarm) or 
falls below the setpoint (LO alarm), then will automatically reset 
when the alarm condition no longer exists.
For a reverse acting alarm, the relay coil is de-energized in a 
non-alarm condition and energized in an alarm condition. The 
alarm activates when the input signal exceeds the setpoint (HI 
alarm) or falls below the setpoint (LO alarm), then automatically 
resets when the alarm condition no longer exists.
When the latching mode is selected, it will be necessary to push 
the functional test button or remove power from the module to 
reset the alarm. The alarm will only reset if the alarm condition 
no longer exists.

Reviews: