22
3.2.7 Reading Adjust Menu
Figure 3.6 Flow Chart for Reading Adjust Menu
ENTER READING ADJUST MENU:
Press
a
1)
Press
a
, if necessary, until
CNFG
prompt appears.
Press
d
2)
Display advances to
INPT
Input Menu.
Press
a
3)
Press
a
, if necessary, until Display advances to
R.ADJ
Reading Adjust Menu.
READING ADJUST VALUE SUBMENU:
Press
d
4)
Display flashes 1
st
digit of previous Reading Adjust value.
Press
b
&
c
5)
Press
b
and
c
buttons to enter a new Reading Adjust value
(-19.99 to 99.99).
Press
d
6)
Display shows
STRD
stored message momentarily and then
advances to
SP.DV
Setpoint Deviation Menu.
Reading Offset Adjust
For Relative Humidity, the unit allows the user to fine tune a minor error of the
transducer, however some applications may require a large offset adjust.
(Displayed Process Value = Measured Process Value ± R.ADJ).
R.ADJ is adjustable between -19.99 to 99.99
This will adjust humidity or temperature depending on Sensor selection, in
Reading Configuration (see
Section 3.2.4
).
3.2.8
SETPOINT DEVIATION ENABLE/DISABLE SUBMENU:
Figure 3.7 Flow Chart for Setpoint Deviation Menu
Press
d
1)
Display advances to Setpoint Deviation
ENBL
Enable or
DSBL
Disable Submenu and flashes the previous selection.
Press
b
2)
Scroll through the available selections:
ENBL
or
DSBL
.
Press
d
3)
Display shows
STRD
stored message momentarily and then
advances to
ID
ID Code Menu.
Setpoint Deviation
Submenu, if “enabled”, allows changes to Setpoint 1 to be made
automatically to Setpoint 2. This mode is very helpful if the Process Value changes
often. In Setpoint Deviation Mode, set SP2 a certain number of degrees or counts
away from SP1 - this relation remains fixed when SP1 is changed. For instance:
Setting SP1=200 and SP2=20 and enabling
SP.DV
means that the absolute value of
SP2=220. Moving SP1 to 300, the absolute value of SP2 becomes 320.