21
3.2.6 Alarm 2
This unit is equipped with two physical outputs that can only be configured as
follows:
Alarm 1 & Alarm 2.
Alarm 2 only works for Temperature, not Humidity.
Figure 3.5 Flow Chart for Alarm 2
ENTER ALARM 2 MENU:
Press
a
1)
Press
a
, if necessary, until
CNFG
prompt appears.
Press
d
2)
Display advances to
RDG
Reading Configuration Menu.
Press
a
3)
Press
a
, if necessary, until Display advances to
ALR2
Alarm 2
Menu.
Press
d
4)
Display advances to Alarm 2
ENBL
Enable or
DSBL
Disable
Submenu.
ALARM 2 ENABLE/DISABLE SUBMENU:
5)
Display flashes previous selection. Press
b
until
ENBL
displays to use Alarm 2.
Press
d
6)
Display shows
STRD
stored message momentarily and then
advances to
ABSo
only if it was changed, otherwise press
a
to
advance to
ABSo
Absolute/Deviation Submenu.
If
DSBL
Alarm 2
Disabled
was selected, all submenus of Alarm
2 will be skipped and meter advances to
R.ADJ
Reading Adjust
Menu.
The remaining Alarm 2 menu items are identical to Alarm 1 Menu.
Modifying Alarm Settings will not reset the instrument.