5
Technical Information
2.4 Cooling and Heating Data Sheet in Rated Frequency
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 7.5 m.
Rated cooling
condition(°C)
(DB/WB)
Model
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe
temperature of heat
exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Compressor
frequency
(Hz)
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
27/19
35/24
36K
0.9 to 1.2
12 to 14
43 to 41
Super High
High
56
Rated heating
condition(°C)
(DB/WB)
Model
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe
temperature of heat
exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Compressor
frequency
(Hz)
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
20/-
7/6
36K
2.0 to 2.5
40 to 39
2 to 5
Super High
High
60
Cooling:
Heating: