LVR300 Series

Programming Positions & Operation

On power-up, the company logo is displayed, followed by the preset level/unit measurement. Changing the level (by float movement)
will be reflected in the display. If the level is at either of the preset switch levels S1 or S2 (the upper and lower levels), the display will
also be alternating between the S1 (or S2) status indication with the level reading. The Switch Active status is also indicated by a
flashing LED.

By rotating the program ring to Position 1 (P1, toward the left) and then back to Neutral, the pro-
gram steps to the S1 setting. The level for activation of the S1 switch is indicated, and may be
edited by turning the program ring to the P2 position (see below). This will highlight the tenths
digit. The digit value is advancing by alternating the program ring from center to the right P2
position. Turning the ring to the P1 position accepts that value and moves to the next digit.
Turning the ring to Neutral and then back to P1 will cycle through all of the digits and then accept the
values.

PROGRAMMING POSITIONS

The P1 to Neutral movement steps the program through positions in the following sequence:

Program

Position 1

Program

Position 2

Neutral

1

2

###.#

Inches (cm)

###.#

< S1

S1

###.#

S1

Min. (Max.)

Hyst 1

##.#

S2

###.#

S2

Max. (Min.)

Hyst 2

##.#

Code

000

###.#

Inches (cm)

Filter

##.#

Units

Inch (cm)

Output

4-20 mA

Logo display, only shown on initial power-up.

Current float level. At right, the switch active status is indicated and alter-
nates with the regular measurement display, and the LED is flashing.

Switch point 1 is active if the level
is below (or below) S1.

Switch point 2 is active if the level
is above (or below) S2.

Switch point 1 value, 
sets level for activation.  

Hysteresis threshold added to
switch point 1 for switch = active.

Hysteresis threshold added to
switch point 2 for switch = active.

Returns to regular display 
of current float level.

To access other program para-
meters, rotate ring to P2 
and change 000 to 111.

Switch point 2 value, 
sets level for activation.  

MODIFYING OPERATING PARAMETERS

From any of the Programming Position steps noted at left, follow
these steps to modify the operating parameter: 

1

Turn the programming ring to the right to Position 2, and then
back to Neutral, to bring up the editing cursor in the first deci-
mal place.

2

Turning the ring to the right and back to Neutral increases the
current decimal place to the next highest value.

3

Turning the ring to the left and back to Neutral moves the cur-
sor on to the next decimal position. Repeat step 2 to edit the
current position.

4

To confirm the new value, continue to turn the ring to the left
and back to neutral until you cycle through all of the decimal
places and the next parameter shows on the display.

ENTERING ADDITIONAL PROGRAM PARAMETERS

After reaching the Code step, enter 111 by turning the ring P1 to
Neutral, and you can access these additional parameters: 

OR

Note: During the programming process, if there is no new action
taken within 30 seconds, the sensor will return to “measurement
display” without saving your changes. You will have to go through
the entire program a second time to re-program the unit.

Time for the mea-

surement to

respond (seconds)

Switch between inches

and cm; Switch points are

converted automatically

Switchable to

0-20 mA

1

2

3

4 mA

###.#

20 mA

###.#

###.#

Inches (cm)

Set the 4 mA level

(may be higher than

the min. level)

Set the 

20 mA level

Returns to regular dis-

play mode

4

5

6

Enter Code 989 to return to Factory Default Settings.

Step-by-step program examples are illustrated on the following pages.

PROTECTING YOUR PROGRAMMING PARAMETERS

1. Pull off the ring. Keep it as a

personal key.

2. Use ring in reverse position 

on the sensor (PROG.LOCK
position).

LOGO

Summary of Contents for LVR300 Series

Page 1: ...omega com e mail info omega com For latest product manuals omegamanual info LVR300 Series Continuous Level Switch System Shop online at User sGuide LVR300 Series...

Page 2: ...78280 Guyancourt France TEL 33 0 1 61 37 2900 FAX 33 0 1 30 57 5427 Toll Free in France 0800 466 342 e mail sales omega fr Germany Austria Daimlerstrasse 26 D 75392 Deckenpfronn Germany TEL 49 0 7056...

Page 3: ...nt accuracy The signal is displayed with units using a back lit LCD graphical display and converted to a 4 20 mA signal Two switch points with either a positive or negative output can be programmed ov...

Page 4: ...s threshold added to switch point 1 for switch active Hysteresis threshold added to switch point 2 for switch active Returns to regular display of current float level To access other program para mete...

Page 5: ...output range in the selected unit Filter for display and analog output It is a FIFO filter and the time to accomplish the actual measurement value corresponds to the seconds shown in the display In r...

Page 6: ...2 The pressures and temperatures must take into consideration possible surges in the temperature and pressure of the system 3 The liquids used must be compatible with the materials of construction Sp...

Page 7: ...therwise shall not exceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequential incidental or special damages CONDITIONS Equipment sold...

Page 8: ...ity Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps Industrial...

Reviews: