To change voltage jumpers:

1. Remove cover from case by carefully

prying up two side tabs using a
screwdriver. Remove two screws from
bottom of case. Slide unit out of case.

2. Locate the main board assembly and

position it in front of you the same
way as shown in Figure 3.1 on the
following page.

3. On the main board, locate the

transformer jumpers W1, W2, and W3
near the transformer T1.

If your power requirement is 115Vac,
jumpers W1 and W2 should be
installed. (

Do not install W3.)

If your power requirement is 230Vac,
jumper W3 should be installed. (

Do not

install W1 or W2.)

Warning!

I

NSTALLATION AND

R

EMOVAL

3

5

DRN-PS Ñ DIN Rail Power Supplies

Summary of Contents for DIN-RAIL DRN-PS-750

Page 1: ......

Page 2: ...sse 26 D 75392 Deckenpfronn Germany TEL 49 0 7056 9398 0 FAX 49 0 7056 9398 29 Toll Free in Germany 0800 TC OMEGASM e mail germany omega com United Kingdom One Omega Drive ISO 9002 Certified River Ben...

Page 3: ...ounting 5 4 Temperature Ranges 5 5 Input Range 5 6 Input Current Surge Protection 5 7 Output Voltage 5 8 Output Current 5 9 Output Ripple 5 10 Temperature Derating 5 11 Power on Indicator 5 12 Short c...

Page 4: ...ammability rating Glass filled polycarbonate case UL 94VO Recessed live parts and connector screws Either 32mm or 35mm DIN rail mounting Jumper select 230V 50Hz or 115V 60Hz input Wide input voltage t...

Page 5: ...C 348 Exceeds VDE551 IEC 742 separation spacing Exceeds VDE106 protective separation Exceeds VDE 160 clearance distances Exceeds VDE160 creepage distances 2 3 Protective Classes IEC 529 IP 20 VDE 106...

Page 6: ...is to be transported then disconnection dismounting and separate packing of the power supply is recommended For units that must be shipped installed on the rail additional bracing to resist transporta...

Page 7: ...it in front of you the same way as shown in Figure 3 1 on the following page 3 On the main board locate the transformer jumpers W1 W2 and W3 near the transformer T1 If your power requirement is 115Vac...

Page 8: ...Board Power Jumpers MAIN BOARD T1 115VAC WIRING SHOWN WITH W1 W3 TRANSFORMER MOUNTING PLATE W2 115VAC JUMPER WIRING W1 W3 W2 230VAC JUMPER WIRING W2 W3 W1 INSTALLATION AND REMOVAL 3 6 DRN PS DIN Rail...

Page 9: ...unting rail guide on the top edge of the mounting rail and lower it to lock it into position Removal Release the spring catch with a screwdriver while raising the module to disengage it installation r...

Page 10: ...4 1 Front Panel Connection Labels shown without regulator cover AC Line AC Neutral Ground RETURN NO CONNECTION 21 5V IN AC N PWR V N C OUT DC INPUT AND OUTPUT CONNECTIONS 4 8 DRN PS DIN Rail Power Su...

Page 11: ...ght Height 2 76 70mm Width 2 95 75mm Depth 5 95 151mm Weight 2 0 lbs 0 9 kg 5 3 Mounting 35mm top hat DIN EN 50022 5 4 Temperature Ranges Operating Temperature Ranges 20 to 60 degrees C Storage Temper...

Page 12: ...5 6 Input Current Surge Protection 6kA 275V Varistor 5 7 Output Voltage 21 5V 2 IR where I output current amperes and R 0 3 5 8 Output Current DRN PS 750 0 750mA 5 9 Output Ripple Less than 10mV pp S...

Page 13: ...Front Panel red LED lamp 5 12 Short circuit and overload protection DRN PS 750 foldback current limiting with automatic high temperature shutdown no fuses required 5 13 Wire Connections Screw down wi...

Page 14: ...5 230vac INPUT V Ground AC Line AC Neutral V A R I S T O R L C F I L T E R B R I D G E 21 5V R E G U L A T O R Return 75mA 50 DRN PS 750 C Ambient 0 1000 800 600 400 200 60 45 35 25 15 5 5 I max DERAT...

Page 15: ...Figure 8 1 Dimensions SPACED AS SHOWN POWER SUPPLY WITH 151 1 5 95 2 76 2 95 3 15 TWO SCREWS FASTEN RAIL UNDER MAX 70 0 75 0 80 0 DIMENSIONS DRAWING 8 13 DRN PS DIN Rail Power Supplies...

Page 16: ...inst excessive energy being drawn from the mains supply in case of a fault in the equipment an overcurrent protection device shall be installed The Protective Conductor must be connected for safety re...

Page 17: ...special damages CONDITIONS Equipment sold by OMEGA is not intended to be used nor shall it be used 1 as a Basic Component under 10 CFR 21 NRC used in or with any nuclear installation or activity or 2...

Page 18: ...M U Totalizers Batch Controllers pH CONDUCTIVITY M U pH Electrodes Testers Accessories M U Benchtop Laboratory Meters M U Controllers Calibrators Simulators Pumps M U Industrial pH Conductivity Equip...

Reviews: