Troubleshooting
Melting water overflows.
Heating pipe for melting water
damaged.
Replace the heating pipe.
Water level controller failure.
Replace the water level controller.
Ambient temperature or humidity
beyond standards.
Improve the conditions.
Normal air curtain, but
periodical fluctuation of
cabinet temperature.
Condenser contaminated.
Clean the condenser.
Poor venting of the unit.
Improve the venting conditions.
Heat protection of compressor failure.
Replace the heat protection.
Capillary is blocked by ice.
Replace the drying filter.
Temperature controller failure.
Replace the temperature controller.
NOTE
Following occurrences are not problems:
•
The murmur of water is heard when the refrigerator is working. It is a normal occurrence as the coolant is
circulating in the system.
•
When the weather is damp, condensation might be found on the outside of the refrigerator. It is caused by
high humidity. Simply use cloth to wipe it off.