Troubleshooting
Maintenance
charged.
COMMON FAULTS AND TROUbLESHOOTING
Fault
Potential cause
Troubleshooting
Not working / indicator is “OFF”.
Power switch not turned on.
Turn on the power switch.
Plug is loose.
Check plug and socket.
The display shows E04 high
temperature / the display shows
E06 high pressure protection.
The ambient temperature is too
high.
Normal working temperature range
of 24°C.
Condenser or air filter is dirty and
blocked.
Clean the condenser and air filter.
High pressure switch wires fallen
off.
Check and correct high pressure
switch wires.
Fan does not start.
Check and correct the fan.
Ice defrost abnormal.
Ambient temperature too low.
Normal working temperature range
of 24°C.
Defrost valve does not start
normally.
Check and correct the defrosting
valve.
Ice thickness too thin or too thick.
Check and correct ice thickness
setting.
Poor transparency of ice cubes; ice
cubes too thin or incomplete.
Ice thickness too thin.
Check and correct ice thickness
setting.
Water pressure too low.
Check that the water supply
pressure is 1.3 bar to 5.5 bar.
Water temperature too high.
Water temperature of 5-35°C.
Inlet water valve does not work.
Check and correct the inlet water
valve.
Inlet water valve is dirty and
blocked.
Check whether water leaks and
correct.
Water leaking.
Check and correct the inlet water
filter.
Inlet water filter has not been
replaced for a long time.
Summary of Contents for IC-CN-0089S
Page 17: ...17 Parts Breakdown Model IC CN 0089S 47773 ...
Page 19: ...19 Parts Breakdown Model IC CN 0129S 47483 ...
Page 21: ...21 Model IC CN 0219S 47484 Parts Breakdown ...
Page 23: ...23 Model IC CN 0289S 47774 Parts Breakdown ...
Page 25: ...25 Model IC CN 0329 47485 Parts Breakdown ...
Page 27: ...27 Model IC CN 0529 46452 Parts Breakdown ...
Page 29: ...29 Model IC CN 0089S 47773 Model IC CN 0289S 47774 Electrical Schematics ...