8.11.4 Actual Position View Mode (View Mode, VI NORM / REVS)
This function is used to set the "RUN AP" value on the LCD to be displayed as direct (NORM) or
reversely (REVS) as the actual position of the valve.
3 seconds
Press <UP> or
<DOWN> button
if the above is not
displayed.
Press <UP> or
<DOWN> button
if the above is not
displayed.
<UP>/<DOWN>
<ESC>
3 times
8.11.5 Factory Reset (dEFAULT oFF / on)
This function initializes all parameters stored in the positioner to initial factory setting. In the dEFAULT
mode, pressing the Enter button for approximately 3 seconds enables ON/OFF setting mode and
then setting it to ON resets all parameters.
Pay attention when using this mode as all the parameter values will be changed to the factory
settings.