922044006_09_024
be performed, the mains power supply
Indication LED status (with connected
and the battery should be connected (the
mains power supply).
battery should be charged). If the battery
is not charged, the test is postponed until
Charge
the battery is completely charged. If
On:
Charge current OK.
during the Automatic Autonomous Test the
Οff:
No battery (No charging current or
luminaire’s duration is lower than the
disconnected battery).
named, then the battery must be
Lamp Fault
replaced.
Οn:
Faulty LED strip.
Off:
LED strip OK.
Back Up Operation
The autonomous duration of battery
Battery Fault
during emergency mode is at least the
Οff:
Battery OK.
one that is stated in the list of the first
Blink
(With
Charge LED
ON): Autonomy
page. During emergency mode, a LED
or low battery problem
(the battery must
strip test is also performed.
be replaced).
Blink
(With
Charge LED
Off):
Resetting Errors
No charging current or disconnected
Push the Test button for 5 seconds, to
battery.
delete all the indicated LED errors. Then
the luminaire enters regular operation
mode.
INSTALLATION INSTRUCTIONS
General
:
1. Operations for installation, maintainance or testing must be done by authorized
personnel only.
2. The device must be connected to the mains power supply through a fuse dependent
by the total amount of the line’s power load.
In case of battery or light source replacement, these must be replaced by parts of the
same type, by the manufacturer or by a competent person.
4
t i
in battery recycling points.
Do not incinerate.
3.
. In case of inactive use for a period greater than 2 months, disconnect the battery by
pulling out the battery’s connector.
5.
I s not allowed to discard batteries in to common trash bins, they must be
discarded only
1
4
3
Remove the front plastic cover by unscrewing the two
retaining screws.
Pass the mains cables through the hole of the plastic base.
Connect the live and the neutral wires to the terminal block
as shown in picture.
Mount the device by installing the included mounting
accessories in the holes or use the Α-3018 mounting
springs for suspended seiling mounting.
Install LED strip and batery connectors to the appropriate
PCB connectors.
Refit the front plastic cover by srewing the two
removed screws in step 1, and power on the device.
1
2
3
4
5
6
5
2
L
N
NOTE!!
After finishing the installation you must power the device
at least for 24 hours for battery charging to perform