5.3.2 FIND ALL POINTS
This screen handles the procedure for automatic detection and registration of all connected points. There is
the option to scan all loop circuits for points or a specific one. Pressing the
“START”
button, initiates the
procedure for the selected loop. When the process completes the panel will clear all current faults and return
to the home screen. The found points will be registered and belong to the zone corresponding to the loop they
are connected to (LOOP 1 = ZONE 1 etc.). Pressing
“STOP”
the procedure terminates, the points found so
far are registered, all current faults are cleared, and the panel returns to the home screen.
IMPORTANT
When the
“FIND ALL POINTS”
procedure starts,
ALL
previous point configuration is lost.
All connected points must have a unique address, per loop circuit.
Figure 43