TEST
FAULT
LAMP
CHARGE
BATT.
Page
2
from
5
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is
stated in the list of the technical
characteristics. During emergency mode, a
light source test is also performed.
ΑΤΤΕΝΤΙΟΝ
!!!
1. Operations for installation, maintainance
or testing must be done by authorized
personel only
.
2.
The device must be connected to the
ma i n s p o we r sup p ly th ro ugh a fuse
dependent by the total amount of the line’s
power load
.
3. The replacement of the battery and the
light source must be done using parts of the
same type, by the manufacturer or by a
competent person.
4
.
In case of inactive use for a period
greater than 2 months, disconnect the
b a t t e r y b y p u l l i n g o u t t h e b a t t e r y ’s
connector.
5
.
I
s not allowed to discard batteries
t i
into common trash bins, they must
b e d i s c a r d e d o n l y
i n b a t t e r y
recycling points. Do not incinerate.
NOTE:
LED= Light Emitting Diode
LABELING EXPLANATION:
X:
Self contained
0:
Non maintained
(*)
A:
Including test device
90:
1.5 hour duration
180:
3 hour duration
(*)
Non Maintained operation:
The luminaire
lights its illumination source, only in power
supply’s failure.
Maintained operation: The luminaire lights its
illumination source, when it is powered by
the mains power supply or not
.
The light source contained in this
luminaire shall only be replaced by the
manufacturer, or his agent, or a
similar qualified person.
INSTALLATION INSTRUCTIONS
Initial installation
1
Untighten the screw but do not remove it and pull up the reflector.
2
Always use in any case round mains cable
,
with a diameter
of 5
-
10mm (H05RN-F
type 2x1mm²
or
any
other type
,
at least
equal
to it’s mechanical and electrical properties).
ATTENTION!! The cable must not be deformed in any way (This requirement is important
to ensure the
ΙΡ
65).
Install
the included gaskets in to the cable entry holes
(verify that are
not deformed)
. Make a hole in the center by using a small screwdriver. Pass the round cable
through the gasket. Tighten the cable gland to form the seal. Detach the power terminal, connect
the wires as shown in the
picture 2 and attach the power terminal.
3
Place the battery’s connector to the corresponding connector on the P.C.B.
4
Refit the reflector (mind the correct orientation), tighten the screw securely and the luminaire
is ready for mounting
.
NOTE!! After finishing the installation you must power the luminaire at least for 24 hours for
battery charging to perform the nominal autonomy.
230V AC
230V AC
N L
3
1
1
Cable
entry
holes
923298002_09_003
2