GENERAL

o

These  devices  are  used  indoors 

(

ta  40 C

)

  in 

places  where  emergency  luminaires  are 
needed. The luminaires

 

GR-290/WP and GR-

292/WP are suitable for corridors lighting and 
the

 

GR-291/WP  and  GR-293/WP  for  open 

a r e a   l i g h t i n g

.

  E a c h   d e v i c e   m u s t   b e  

permanently  connected  to  mains  power 
supply

.

  In  normal  operation  the  battery  is 

charging.  In  case    of  a  mains  power  supply 
failure    the  device  will  light  the  illumination 
led  automatically  in  emergency  mode.  When 
the    mains    power    supply  is  restored  the 
device turns to normal operation.

INSTALLATION

To  install  the  luminaire  follow  the  installation 
instructions 

ο

n page 2.

Battery Charging

The battery charging is completely controlled

In  this  case,  is

 

achieved  the  perfect    battery 

maintenance 

as well as the elongation of its 

duration

When  the  battery  has  completely 

charged

it  charges  with  a  maintenance 

current.

Battery Cut-off

The device in this operation when the mains 
power  supply  fails

 

and  battery  has  lost  its 

energy

During  this  operation  the  device 

enters  the  idle  state

 

and  battery  consumption 

is  negligible,  in  order  to  be  protected  from 
deep discharge.

Automatic Operational Test

It is conducted automatically every 15 days. In 
order  to  be  performed,  the  mains  power 
supply and the battery should be connected.
       

Automatic Autonomous Test

The Automatic Autonomous Test is conducted 
and measures the device’s back up operation 
and  emergency  duration.  The  BATTERY 
FAULT  LED  blinks  during    the  measurement, 
indicating this process to the user. This test is 
conducted  automatically  every  six  months

In 

order  to  be  performed,  the  mains  power 
supply  and  the  battery  should  be  connected 
and  fully  charged

If  the  battery  is  not  fully 

charged

the test is postponed

 

until the battery 

is    completely  charged.  If  during  this  test,  the 
autonomy  is  less  than  the  nominal  then  the 
battery  fault  led  turned  on  continuously  and 
the battery must be replaced.
 

Back Up Operation

The  autonomous  duration  of  battery  during 
emergency  mode  is  at  least  the  one  that  is 

WATERPROOF SELF TESTING  NON MAINTAINED SPOT LIGHT 

EMERGENCY LUMINAIRES WITH 1 WHITE POWER LED

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL

EXTERNAL DIMENSION
WEIGHT

GUARANTEE

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERY (Ni-MH)

CHARGE TIME

INDICATIONS - CONTROLS

BATTERY PROTECTION

MINIMUM DURATION

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

EMERGENCY ILLUMINATION

LIGHT SOURCE

220-240V AC / 50-60Hz

3 hours

1.5 hour

24 hours

Deep discharge and overcharge protection

IP65

4.8V/1.2Ah

  270lm 

  160lm 

  1 white

 

power LED

o

5 to 40  C

Up to 95% 

ABS/PC, PC

3 years

 (1 

year for the battery

)

430gr.

Ø125 x 65 mm

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

Charge, lamp fault, battery fault

TEST button

 GR-29

0

/WP

 GR-291/WP

 GR-292/WP

 GR-293/WP

3.7W / 4.1 VA

TECHNICAL CHARACTERISTICS

 

(for LED MODULE specifications see page 4)

Thank you for your trust in our products  

Olympia Electronics - European manufacturer

923293005_09_004