Figure 4
Figure 1
Figure 3
Non-maintained
operation
Maintained
oparation
1.
To instal the device you have to dismantle carefully the device with a flat screwdriver as
shown in figure 1.
2.
Pass the mains cables through the hole (point 1 in figure 2)
.
The luminaire must be
connected to a permanent electrical installation
to ensure
the
immobilization of the cable.
3.
Mount the base plastic on the wall by using the included mounting accessories in points 2
and 3 in figure 2.
4.
Connect the battery`s cable with the appropriate terminal (figure 3).
5.
Connect the mains cables to the terminal block as shown in figure 4
.
6.
Refit with care the removed plastic parts and power on the luminaire
.
NOTE!!
After finishing the installation you must power the luminaire at least for 24 hours for
battery charging to perform the nominal autonomy.
4
Installation instructions
Connection terminal
block on the PCB
For fuce ratings
see text
Battery replacement
.
It can be done only by a competent person and after the mains supply interruption
.
1.
Dismantle the device
(step 1 of
the installation
instructions)
.
2. Disconnect the connector and remove the old battery.
3. Connect the new battery with the same type (step
4
of the installation
instructions
) and
place it in the position of the old one.
4. Follow the step
6
of the installation procedure and power the device.
(*)
Maintained operation: The luminaire lights its
illumination source, when it is powered by the mains
power supply or not
.
Non Maintained operation: The luminaire lights its
illumination source,
only in power supply’s failure.
Note!! T
he installer should fill in
, on the specification label,
the letter
G
if the luminaire is used as a safety sign
.
X
1
1 8
0
A
G
NOTE:
LED= Light Emitting Diode
LABELING EXPLANATION:
X:
Self contained
1:
Maintained
(*)
A:
Including test device
G:
Internally illuminated
18
0:
3
hours duration