Connecting a BSR-8020/WP with detectors ΒS-685 or ΒS-686. The auxiliary relay is 
used so as to interrupt the power to the detectors after a panel reset.

24V power supply

from panel

56k

Ω

10k

Ω

Loop

Loop

Operate as a Input unit

Operation

Dip-switch setting

Relay is activated for

5 seconds after a reset

1

ON

2 3 4 5 6 7 8 9 10

1

ON

2 3 4 5 6 7 8 9 10

The relay is activated

only when the input 

is activated

BS-685 

or

BS-686

BS-685

or

BS-686

+24V

 IN

NO

+IN

C

-IN

NC

ON

OFF

+L+L+L

-L

PE

PE

+L+L+L

-L

Connecting gas detectors

921802002_09_005

Summary of Contents for BSR-8020/WP

Page 1: ...lity to send to the panel with a suitable connection three states quiescent fault alarm 6 Reinstall the front cover and fasten the screws that were removed in step 1 The output unit contains a fully p...

Page 2: ...which blinks periodically in the quiescent state is a power and good operation indication On the panel the input unit is shown as INPUT OUTPUT UNIT where is the set address of the device In this func...

Page 3: ...On the 24V IN terminal you can connect an external power supply if the function conventional detector driving unit with external power supply is selected Indication LED Blinks periodically in quiescen...

Page 4: ...3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4...

Page 5: ...th an isolation lock When the lock is activated short circuit the output of the device does not operate and the message DISABLEMENT is shown on the panel The dip switch 8 of the BSR 8020 WP must be in...

Page 6: ...wer supply from panel 56k 10k Loop Loop Operate as a Input unit Operation Dip switch setting Relay is activated for 5 seconds after a reset 1 ON 2 3 4 5 6 7 8 9 10 1 ON 2 3 4 5 6 7 8 9 10 The relay is...

Page 7: ...24V IN NO IN C IN NC ON OFF L L L L PE PE L L L L Connecting a BSR 8020 WP with conventional detectors A 10k terminal resistor must be connected on the last detector The maximum number of detectors p...

Page 8: ...stalled on the last detector The maximum number of detectors per device is 40 conventional detectors of olympia electronics According to EN 54 the maximum number of detectors per zone is 32 devices Th...

Page 9: ...be returned to the premises of our company for repair or replacement as long as the warranty period is valid 72nd km O N R Thessaloniki Katerini WARRANTY HEAD OFFICE www olympia electronics com Olympi...

Reviews: