Dip-switches

9 & 10

Operating mode

Input/Output unit

Input unit

 

Conventional detector driving unit

Conventional detector driving unit with external power supply

 

4) Conventional detector driving unit with external power supply. 

The above functions are set using the dip-switches 9 and 10. The dip-switch 8  determines a 
sub function depending on the case.

1) Input/Output Unit

In this function input and output units are independent. 

The device has 4 different operation modes:

2) Input unit 

OPERATION

The input unit with auxiliary relay is used so as to provide an additional input to the loop. Gas 
sensor types BS-685 and BS-686 can also be connected. It contains an input that is fully 
monitored for open and short circuit conditions and a relay (1A/30V), which is activated for 5 
seconds after a panel reset (when the dip-switch number 8 is in the OFF position). On the 
panel, the input units are shown as  “INPUT UNIT ΧΧΧ” (where ΧΧΧ is the set address of the 
device). In this function, the terminal resistor is 56kΩ and the alarm resistor is 10kΩ. 

The input unit is used in order to connect non addressable devices, that have a free relay 
contact (such as conventional alarm panels, or flow switches), to the loop of the panel. The 
input  unit  is  fully  monitored  and  has  the  capability  to  send  to  the  panel,  with  a  suitable 
connection, three states: quiescent, fault, alarm. The output unit contains a relay that is fully 
programmable from the panel with a rating of (30V/1A). The red LED which blinks periodically 
in the quiescent state is a power and good operation

 

indication. On the panel, the input unit is 

shown as “INPUT/OUTPUT UNIT  ΧΧΧ” (where ΧΧΧ is the set address of the device). In this 
function, the terminal resistor is 56kΩ and the alarm resistor is 10kΩ. 

3) Conventional detector driving unit

The driving unit for conventional detectors is used in order to connect conventional detectors 
to the addressable panel. The device can be connected to the BSR-2104 and BSR-2114 
panels. It can power up to 10 detectors and has protection against the detection of an open 
circuit  or  the  disconnection  of  a  detector.  A  56kΩ  resistor  is  installed  by  default  on  the 
terIN, -IN. We replace the 56k

Ω 

resistor with a 10k

Ω 

resistor. We install the 10k

Ω 

resistor to the last detector of the line. On the panel, the input unit is shown as ``ADAPTOR 
UNIT   ΧΧΧ`` (where ΧΧΧ is the set address of the device). The LED lights and remains lit 
when the specific input unit issues an alarm to the panel. The LED also remains lit if the sirens 
are deactivated from the panel. The LED of the detector that issued the alarm also remains lit 
in  order  to  show  the  precise  alarm  origin.  LED  is  turned  OFF  after  a  panel  reset.  In  this 
operation we have increased consumption and cannot connect more than 7 BSR-8020/WP 
on each loop. In this function the terminal resistor is 10kΩ and the alarm resistor is 1kΩ . 

This function is the same as the previous one. The only difference between the two, is that an 
external power supply is used. The external power source must have an output rating of 21-
28V and must not be interrupted during a power failure.In this function the terminal resistor is 
4.7kΩ and the alarm resistor is 1kΩ . 

921802002_09_005

Summary of Contents for BSR-8020/WP

Page 1: ...lity to send to the panel with a suitable connection three states quiescent fault alarm 6 Reinstall the front cover and fasten the screws that were removed in step 1 The output unit contains a fully p...

Page 2: ...which blinks periodically in the quiescent state is a power and good operation indication On the panel the input unit is shown as INPUT OUTPUT UNIT where is the set address of the device In this func...

Page 3: ...On the 24V IN terminal you can connect an external power supply if the function conventional detector driving unit with external power supply is selected Indication LED Blinks periodically in quiescen...

Page 4: ...3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4...

Page 5: ...th an isolation lock When the lock is activated short circuit the output of the device does not operate and the message DISABLEMENT is shown on the panel The dip switch 8 of the BSR 8020 WP must be in...

Page 6: ...wer supply from panel 56k 10k Loop Loop Operate as a Input unit Operation Dip switch setting Relay is activated for 5 seconds after a reset 1 ON 2 3 4 5 6 7 8 9 10 1 ON 2 3 4 5 6 7 8 9 10 The relay is...

Page 7: ...24V IN NO IN C IN NC ON OFF L L L L PE PE L L L L Connecting a BSR 8020 WP with conventional detectors A 10k terminal resistor must be connected on the last detector The maximum number of detectors p...

Page 8: ...stalled on the last detector The maximum number of detectors per device is 40 conventional detectors of olympia electronics According to EN 54 the maximum number of detectors per zone is 32 devices Th...

Page 9: ...be returned to the premises of our company for repair or replacement as long as the warranty period is valid 72nd km O N R Thessaloniki Katerini WARRANTY HEAD OFFICE www olympia electronics com Olympi...

Reviews: