GENERAL

The  red  LED  which  blinks  periodically  in  the  quiescent  state  is  a  power  and  good  operation  indication. The

 

LED 

lights and remains lit when the specific input unit issues an alarm to the panel.

 

The 

LED 

remains also lit 

when  the  sirens  are  deactivated  from  the  panel  in  order  to  indicate  the  precise  point  where  the  alarm 
originated  from.  The  Led  is  turned  OFF  after  a  panel  reset

.

  Each  device  must  have  an  address,  that  is 

recognized by the panel. It is not allowed for two devices on the same loop to have the same address. Page 4 
contains  the  full  table  that  shows  the  addresses  and  the  setting  with  the  dip-switches.  Up  to  127  units  can 
connected to each panel

.

4

. Notice!! If an additional entry hole is required then remove the break-out plastic and install the supplied

The input-output unit is recognized and programmed by the BSR-2100 panel. This device is used in order that 
non-addressable  devices  that  have  a  free  relay  contact  (such  as  fire  alarm  panels,  flow  switches  and 
conventional detectors) to be connected on the loop

The input unit is fully monitored and has the capability to 

send to the panel, with a suitable connection, three states: quiescent, fault, alarm.

6.

 Reinstall the front cover and fasten the screws that were removed in step 1. 

The output unit contains a fully programmable by the panel relay with a rating of (30V/1A). 

INSTALLATION

   

(

Notice!!! The mounting accessories are included).

 

1

.

 

Unfasten the front cover screws and remove the cover. 

5.

 Set the address on the dip-switch (page 4 and 5).   

3

. Pass the cables through the cable glands and make the required connections.

    cable gland.

2

. Locate the mounting holes and use the supplied accessories to mount the unit on the required position. 

21-28V

ABS/PC

ALARM CONSUMPTION WHEN USED AS A CONVENTIONAL DEVICE DRIVER

QUIESCENT CONSUMPTION WHEN USED AS A CONVENTIONAL DEVICE DRIVER

30

mA

5

.

6

mA

IP65

1.

3

mA (with activated LED)

o

-

10 to 60  C

Up to 95% 

2 years

170

gr.

155x80x43mm

EN 54-1

8

TECHNICAL CHARACTERISTICS

RELATIVE HUMIDITY
CONSTRUCTIONAL MATERIAL

WEIGHT

DIMENSIONS

GUARANTEE

OPERATION VOLTAGE
QUIESCENT CONSUMPTION
ALARM CONSUMPTION 

PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE

DEGREES OF COVER PROTECTION 

0.

7

mA

INSTALLATION

EXTERNAL POWER SUPPLY

For internal use only

21-28V

Olympia Electronics - European manufacturer

Thank you for your trust in our products

Indicator LED

4

BSR-8020/WP Waterproof Addressable input-output unit

2

2

3

3

5

1

Summary of Contents for BSR-8020/WP

Page 1: ...lity to send to the panel with a suitable connection three states quiescent fault alarm 6 Reinstall the front cover and fasten the screws that were removed in step 1 The output unit contains a fully p...

Page 2: ...which blinks periodically in the quiescent state is a power and good operation indication On the panel the input unit is shown as INPUT OUTPUT UNIT where is the set address of the device In this func...

Page 3: ...On the 24V IN terminal you can connect an external power supply if the function conventional detector driving unit with external power supply is selected Indication LED Blinks periodically in quiescen...

Page 4: ...3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4...

Page 5: ...th an isolation lock When the lock is activated short circuit the output of the device does not operate and the message DISABLEMENT is shown on the panel The dip switch 8 of the BSR 8020 WP must be in...

Page 6: ...wer supply from panel 56k 10k Loop Loop Operate as a Input unit Operation Dip switch setting Relay is activated for 5 seconds after a reset 1 ON 2 3 4 5 6 7 8 9 10 1 ON 2 3 4 5 6 7 8 9 10 The relay is...

Page 7: ...24V IN NO IN C IN NC ON OFF L L L L PE PE L L L L Connecting a BSR 8020 WP with conventional detectors A 10k terminal resistor must be connected on the last detector The maximum number of detectors p...

Page 8: ...stalled on the last detector The maximum number of detectors per device is 40 conventional detectors of olympia electronics According to EN 54 the maximum number of detectors per zone is 32 devices Th...

Page 9: ...be returned to the premises of our company for repair or replacement as long as the warranty period is valid 72nd km O N R Thessaloniki Katerini WARRANTY HEAD OFFICE www olympia electronics com Olympi...