detected the alarm is visible. They are turned off only when a reset command is given from the panel. The 
indicator led blinks every 10 sec indicating the connection status with the main panel.

SETTING THE ADDRESS

Each detector must have a unique address, with which it is recognised from the panel. It is forbidden for 
two devices in the same loop to have the same address. To set it up you can use the function of changing 
address point 

as described in the user manual of the panel.

.


Dust compensation and automatic generation of cleaning notifications. Stable level of 
detection regardless of detector’s working hours.

Compensation of smoke measurements based on ambient temperature which ensures high 
precision measurements even under extreme environmental conditions

Automatic fault diagnosis.

Adjustable smoke and temperature alarm level for maximum flexibility.

360  

UID: 

In every device there is a double sticker with the UID (Unique Identifier) number. This number is 
unique for each device.

INSTALLATION

The detectors should be placed in the ceiling in visible points without side obstacles, away from places 
that are barely ventilated or with strong air currents and water vapor. Each detector  covers an area of 50 

2

m  while the distance between two detectors should not be more than 15m. Also, they must be placed at 
least 50 cm away from fluorescent lamps. Cable diameter should be from 

. to  .

MAINTENANCE & FUNCTIONAL TESTING

The detector has fault diagnosis and dust compensation functions, which automatically informs you when 
replacement or cleaning actions are required. These functions combined with periodic manual testing 
ensure maximum security level. The manual testing procedure is carried out by spraying a small amount 
of smoke into the detector with an A-752 spray or a counterpart product. It is suggested to carry out a test 
every 6 months or after a change in the position of the sensor. A key element of its proper function is the air 
to be able to freely circulate inside it. So be careful not to block the openings of the outer cover. Before the 
manual testing it is suggested to enable the special “walk in test” mode from the panel.

CAUTION !!

After installation the device must not be covered with dust or be painted or anything else happen that will 
block the smoke to get to the sensor. Special attention must be given during the installation and the use of 
the device, since the user assumes full responsibility for proper operation afterwards.
Also, during site works place the plastic cover to the detector as shown in the picture below to protect the 
device from dust.

0 5 

2 5mm

Additional features of the device

 

:

o

optically visible LED.

Integration of dynamic algorithms for noise and false alarm rejection.

Page

 

2 from

 4

921

6

1

57

00_0

9

_00

3

Summary of Contents for BSR-6157

Page 1: ...o the user can selectA1R orA2S working mode through the panel They are composed by two parts A plastic base which is placed on the ceiling and the main body of the o detector which fits on the plastic base with a simple rotation to the right The detectors have a 360 visible led and a remote led driver which are light up constantly in case of detection of fire till cancelled from the panel Also the...

Page 2: ... more than 15m Also they must be placed at least 50 cm away from fluorescent lamps Cable diameter should be from to MAINTENANCE FUNCTIONALTESTING The detector has fault diagnosis and dust compensation functions which automatically informs you when replacement or cleaning actions are required These functions combined with periodic manual testing ensure maximum security level The manual testing proc...

Page 3: ...ce and after 3 5 seconds it is ready for operation CONNECTION 1 IN OUT Connect to L of the loop 2 IN Connect to L of the loop 3 OUT Connect to L of the loop 4 R External LED connection 5 Connected to the cable s shield when shield is used Mounting base Figure 1 5 5 R R Installation process 2 Connection with exterrnal LED UT O N I N I T U O Side marks Page 3 from 4 eni t n s g a f d t e n ta e c m ...

Page 4: ... any repairs or re setting done by a third party unless Olympia Electronics has fully agreed to them in writing Products that have been damaged can be returned to the premises of our company for repair or replacement as long as the warranty period is valid Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of def...

Reviews: