detected the alarm is visible. They are turned off only when a reset command is given from the panel. The
indicator led blinks every 10 sec indicating the connection status with the main panel.
SETTING THE ADDRESS
Each detector must have a unique address, with which it is recognised from the panel. It is forbidden for
two devices in the same loop to have the same address. To set it up you can use the function of changing
address point
as described in the user manual of the panel.
.
-
-
Dust compensation and automatic generation of cleaning notifications. Stable level of
detection regardless of detector’s working hours.
-
Compensation of smoke measurements based on ambient temperature which ensures high
precision measurements even under extreme environmental conditions
.
-
Automatic fault diagnosis.
-
Adjustable smoke and temperature alarm level for maximum flexibility.
-
360
UID:
In every device there is a double sticker with the UID (Unique Identifier) number. This number is
unique for each device.
INSTALLATION
The detectors should be placed in the ceiling in visible points without side obstacles, away from places
that are barely ventilated or with strong air currents and water vapor. Each detector covers an area of 50
2
m while the distance between two detectors should not be more than 15m. Also, they must be placed at
least 50 cm away from fluorescent lamps. Cable diameter should be from
. to .
MAINTENANCE & FUNCTIONAL TESTING
The detector has fault diagnosis and dust compensation functions, which automatically informs you when
replacement or cleaning actions are required. These functions combined with periodic manual testing
ensure maximum security level. The manual testing procedure is carried out by spraying a small amount
of smoke into the detector with an A-752 spray or a counterpart product. It is suggested to carry out a test
every 6 months or after a change in the position of the sensor. A key element of its proper function is the air
to be able to freely circulate inside it. So be careful not to block the openings of the outer cover. Before the
manual testing it is suggested to enable the special “walk in test” mode from the panel.
CAUTION !!
After installation the device must not be covered with dust or be painted or anything else happen that will
block the smoke to get to the sensor. Special attention must be given during the installation and the use of
the device, since the user assumes full responsibility for proper operation afterwards.
Also, during site works place the plastic cover to the detector as shown in the picture below to protect the
device from dust.
0 5
2 5mm
Additional features of the device
:
o
optically visible LED.
Integration of dynamic algorithms for noise and false alarm rejection.