                         ADDRESSABLE OPTICAL SMOKE DETECTOR

103 (diam.) x 48 (height)

 mm

Alarm LED 

to external LED driver (BS-572)

0.120dB/m

IP20

EN 54-7

o

-10 to 60  C

Up to 95% 

2 years

160gr.

TECHNICAL CHARACTERISTICS

 BSR-6055/A

IDLE STATE POWER CONSUMPTION
ALARM POWER CONSUMPTION
SENSITIVITY

PRODUCED IN ACCORDANCE WITH

OPERATION TEMPERATURE RANGE

DEGREES OF COVER PROTECTION

OPERATION VOLTAGE

RELATIVE HUMIDITY

TYPICAL WEIGHT 

EXTERNAL DIMENSIONS 

GUARANTEE

INDICATORS
OUTPUT

921605502_09_015

Page 1 from 2

21-28V DC

1.5 mA (with indication LED activated)

1mA

GENERAL

Before  installing  the  detector,  the  user  must 
read these instructions carefully and store this 
manual for future  reference.
BSR-6055/A is an addressable optical smoke 
detector.  It  co-operates  with  BSR-1116    and 
BSR-2100  panels.  The  device  transmits  an 
analogue value to the panel which   depends 
on the amount of the smoke that there is in the 
area.  The  analogue  value  is  100  with 
obscuration rate 0.120dB/m (small amount of 
smoke).
The factory setting of  the panel is to issue an 
alarm  when  the    analogue  value  is  greater 
than 110.

The  user  can  change  from  the  panel  this 
analogue value from 100 (high sensitivity) up 
to 120 (low sensitivity).

They have two parts, one plastic base which is 
installed on the ceiling and the main unit of the 
detector  which  is  fastened  to  the  base  by  a 
simple turning to the right.                
The detectors have an   indication   led which 
lights  continuously  in  case  of  fire  detection 
until  there  is  a  reset  signal  from  the  panel.   
When we silence the sirens the LED remains lit 
to show us the detector that issued the alarm. 
The LED goes off when we RESET the panel. 
The indication led also flashes every 8 sec to 
indicate good operation.

ADDRESS SETTING

To set each detector’s address you have to use 
the  device  BSR-2143  photo.  1.  (refer  to  it’s 
instruction manual). After the address setting   

mark  this  number  to  the  sticker  on  the 
detector’s  base  (ADR:XXX).  Each  detector 
must  have  an  address  with  which  it  is 
recognized from the panel.
It`s  forbidden  for  two  devices  with  same 
addresses to be connect  to  the  same  loop.  

OPERATION CHECK 

The operation check can be done by spraying a  
small  amount  of  smoke  into  the  detector’s 
chamber.  You  can  use  the  special  smoke 
device  A-752  of  our  company,  or  a  similar 
device. 
It is advised to conduct a good operation test 
every  6  months  and  every  time  the  detector   
position is changed. 
It is essential to have good air circulation inside  
the detector. Therefore care must be taken so   
that the vents of the detector are not covered. 

NOTE

The detectors must be placed in the ceiling on 
visible areas with no side obstacles and away 
from sides with no air circulation or strong air 
currents  and  vapors.  Each  detector  covers 

2     

almost  50  m

and  the  distance  between  two 

detectors  must  not  exceed  15m.  Also  the 
detectors  must  be  placed  away  from 
fluorescent tubes at least 50 cm.
The cables cross section must be from 0.5 to 

2

1.5mm . 

ATTENTION!!

After  the  device  is    installed,  care  must  be   
taken, so that the detector vents are not blocked 
by   anything (i.e. dust, paint). Failing to do   so 
will  prevent  the  smoke  particles  to  enter    the   
detection  chamber.

Thank you for your trust in our products.  