Dimensional drawing (mm)

Installation Instructions

1

3

4

5

2

6

6

1

2

3

127

80

56

17

137

82

Sounder

Package Contents

Adjusting the sounder

Mounting Accessories

General

Manual

This device is used as audible warning sounder in case of fire event. The sound level covers an 
area  of  several  square  meters.  It  is  compatible  with  fire  panels  that  support  Olympia  A 
Protocol. The BSR-51

30

/WP integrates an isolator short circuit which activates automatically 

by disconnecting the defective node from the loop and allowing it’s detection though the 
panel.

Table 1

Sound level No

Switch setting [6-7]

1
2
3
4

0-0
1-0
0-1
1-1

Table 2

Angle of measurement

dB(A)

 

at 1m at Sound level 4

15
45
75

135

105

165

86
92
97
97

88

94

Remove the front plastic cover.

Drill the holes needed to pass the connection cables. Place the cable rubber grommets and open a hole 
to the center with a small screwdriver. Pass the connection cables through the rubber grommets.
Use the supplied mounting accessories to place the base of the siren in height up to 2.3 meters from 
the gound. 

CAUTION!! Make sure that the base of the siren is installed in the correct orientation.

Replace the plastic cover and fasten it with the 
four including screws.

NOTE!!!

  After  finishing  the  installation, 

place the sticker SEAL as shown in the picture 
above.

Remove the second plastic from its base.

Replace  the  plastic  cover  and  fasten  it  with  the 
including red screw.

Rubber sealing ring

Wall Plug

Rubber grommet

Washer
Screw

x

VAD

Cover Area 

Ο

-x-y-z

Wall Mounting

y

z

x=2.3m

y=

2

.

4

m

z=

4

.

8

m

Seal

Terminal connection to the loop.

DIP switches for

siren settings.

l

To 

adjust the type of the sound indication

 use DIP 

switches 1 to 5, according to Table 3.

l

To 

adjust  the  sound  level

  use  DIP  switches  6  to  7, 

according to Table 1.

Test the operation of the device through the panel after the installation.
UID: In every device there is a double sticker with the UID (Unique Identifier) number. 
This number is unique for each device.

921513000_09_005

921513000_09_005

921513000_09_005

·

Lit steady

 in case of alarm.

Indicating LED

·

Flashes

 periodically in quiescent state.

·

Turns off

 only after a 

reset.

Loop

 

OUT

Loop

 

IN

Loop

 

IN

Loop

 

OUT

-R

UT

/

O

N

  I

+

N

  -

   I

T

U

  

  

O

-R

UT

/

O

N

  I

+

N

  -

   I

T

U

  

  

O

-R

UT

/

O

N

  I

+

N

  -

   I

T

U

  

  

O

-R

UT

/

O

N

  I

+

N

  -

   I

T

U

  

  

O

-R

UT

/

O

N

  I

+

N

  -

   I

T

U

  

  

O

1 2 3 4 5 6 7 8

ON

Reviews: