1
1
1
Dimensional drawing (mm)
Installation Instructions
1
3
4
5
2
6
6
1
2
3
127
80
56
17
137
82
Sounder
Package Contents
Adjusting the sounder
Mounting Accessories
General
Manual
This device is used as audible warning sounder in case of fire event. The sound level covers an
area of several square meters. It is compatible with fire panels that support Olympia A
Protocol. The BSR-51
30
/WP integrates an isolator short circuit which activates automatically
by disconnecting the defective node from the loop and allowing it’s detection though the
panel.
Table 1
Sound level No
Switch setting [6-7]
1
2
3
4
0-0
1-0
0-1
1-1
Table 2
Angle of measurement
dB(A)
at 1m at Sound level 4
15
45
75
135
105
165
86
92
97
97
88
94
Remove the front plastic cover.
Drill the holes needed to pass the connection cables. Place the cable rubber grommets and open a hole
to the center with a small screwdriver. Pass the connection cables through the rubber grommets.
Use the supplied mounting accessories to place the base of the siren in height up to 2.3 meters from
the gound.
CAUTION!! Make sure that the base of the siren is installed in the correct orientation.
Replace the plastic cover and fasten it with the
four including screws.
NOTE!!!
After finishing the installation,
place the sticker SEAL as shown in the picture
above.
Remove the second plastic from its base.
Replace the plastic cover and fasten it with the
including red screw.
Rubber sealing ring
Wall Plug
Rubber grommet
Washer
Screw
x
VAD
Cover Area
Ο
-x-y-z
Wall Mounting
y
z
x=2.3m
y=
2
.
4
m
z=
4
.
8
m
Seal
Terminal connection to the loop.
DIP switches for
siren settings.
l
To
adjust the type of the sound indication
use DIP
switches 1 to 5, according to Table 3.
l
To
adjust the sound level
use DIP switches 6 to 7,
according to Table 1.
Test the operation of the device through the panel after the installation.
UID: In every device there is a double sticker with the UID (Unique Identifier) number.
This number is unique for each device.
921513000_09_005
921513000_09_005
921513000_09_005
·
Lit steady
in case of alarm.
Indicating LED
·
Flashes
periodically in quiescent state.
·
Turns off
only after a
reset.
Loop
OUT
Loop
IN
Loop
IN
Loop
OUT
-R
UT
/
O
N
I
+
N
-
I
T
U
-
O
-R
UT
/
O
N
I
+
N
-
I
T
U
-
O
-R
UT
/
O
N
I
+
N
-
I
T
U
-
O
-R
UT
/
O
N
I
+
N
-
I
T
U
-
O
-R
UT
/
O
N
I
+
N
-
I
T
U
-
O
1 2 3 4 5 6 7 8
ON