background image

detector

). 

A terminal resistor (5,6K

Ω)

 should be 

installed on the end of the line(see figure 2).

 

On  the

  EXT  BUZ 

terminal  we  can  connect  an 

external buzzer 

BS-542.

An  external  sensor 

(BS-692,  BS-693)

  can  be 

connected  to  the  terminals

+VS,  GND,  S. 

The 

external  sensor  uses  a  specific  protocol  to 
communicate with the unit.You can connect only 
one external sensor with cable at least diameter 
3*0.75mm  and length no more than 50m.

WARNING

!!

 

If an external sensor is installed then 

the positions 1-2 on JMP2 must be linked.

 

Failing 

to  link  these  two  point  will  result  in  non-
communication  between  the  two  devices.  The 
link should be done when the unit is not operating.

 

Sensitivity

The 

BS-690 

detectors  are  activated  when  the 

content  of  gas  (propane  or  butane),  in  the 
monitored  area,  exceeds 

5  -  15% 

of  the  lower 

explosive level

 (L.E.L). 

The 

BS-691 

detectors  are  activated  when  the 

content of gas (methane), in the monitored area, 
exceeds 

5  -  15% 

ofthe  lower  explosive  level

 

(L.E.L).  

The same detectors can also be used as 

an alcohol vapor detector.

 

The are connected and operate with the mains 

power supply voltage of

 230VAC.

When  the  detector  is  activated,  an  internal 
sounder

(

buzzer)

 

is  sounded  and  the  internal 

relay is activated. The relay can be used to control 
an electro-valve.

 

The buzzer stop sounding when 

the gas content drops below 

 5-15% 

of the 

L.E.L. 

The electro-valve is reset manually.

  

Indications LEDS and operation

  

The green LED shows the presence of the mains 

power supply.

 

When first installed, the green LED 

blinks  for  20  seconds  until  the  sensor 
compensates to its surroundings.

 

When the red LED is lit then the unit is in alarm 

mode

Alarm mode can be triggered from:

  

a

The sensor of the unit

  

b

The external sensor

 (BS-692, BS-693)

  

c

From a fire detection zone

.

When the yellow LED is lit the unit has an fault 
which can because by:

 

a

The  sensor  of  the  unit

(

e.g

Dis-connected 

sensor)

.

 

b

)

The  external  sensor  (e.g.  Communication 

problem)

   

c

The fire detection zone 

 (

e.g. Open or short 

circuit  condition)

.

   

A  blinking  red  LED  means  that  there  was  an 

alarm condition but it has now passed. The same 
applies  for  a  blinking  yellow  LED  and  the  fault 
condition. 

   

When the test button is pressed, the system is 

tested and restarted. During the test the internal 
circuits are checked, the relay is activated and the 
internal buzzer sounds.

 

Also, during the test all 

alarm and fault indications are reset. Finally the 
fire detection zone is reset.

 

   

After  the  test  and  if  an  electro-valve  was 

connected  to  the  unit,  a  manual  reset  of  the 
electro-valve must be done.

Installation of an electrovalve

 

 

The gas supply is automatically turn OFF in the 

event of an alarm or fault condition. The electro-
valve can only be reset manually by the user, by 
pressing  on  point 

“Α”

  as  show  in  figure  1. 

Depending on the type of electro-valve used, the 
corresponding  connection  diagram  is  shown  in 
figure 4.

 

Care must be taken to position the link of 

 

JMP1 

in the correct position

It is suggested that 

this  unit  is  used  in  cooperation  with 

  Οlympia 

Electronics 

Electro-valves  type

  BS-684  (12V 

N.O.)   

Or 

  BS-682  (  230VAC      N.O.). 

The 

connection cable, when you use BS-684,   must 
be  at least 2x2.5mm diameter and no more than 
4m length.

There is a screw behind the plastic cover

Figure

 1. 

Remove the plastic cover

Remove the plastic cover using a flat screwdriver

921691000_

09

_0

16

Page 

 

2 from

 

5

Reviews: