                         OPTICAL SMOKE DETECTOR

18-30V DC

150

μ

A for 50 sec

103

 

(

diam.) x 48 (height)

 mm

0.120dB/m
Alarm LED

To panel / to external LED driver (BS-572)

20-30mA

IP20

EN 54-7

50

μ

A

o

-10 to 60  C

Up to 95% 

2 years

1

6

0gr.

TECHNICAL CHARACTERISTICS

 BS-655

START UP POWER CONSUMPTION
STAND BY POWER CONSUMPTION
ALARM POWER CONSUMPTION

PRODUCED IN ACCORDANCE WITH

OPERATION TEMPERATURE RANGE

DEGREES OF COVER PROTECTION

OPERATION VOLTAGE

RELATIVE HUMIDITY

TYPICAL WEIGHT 

EXTERNAL DIMENSIONS 

GUARANTEE

SENSITIVITY
INDICATORS
OUTPUT

921655000_23_018

Page

 

2 from

 

2

1. 

Detach the detector from it’s base by turning it anticlockwise until the side marks are aligned.

2. 

Install the base with the included mounting parts (point 5)

.

3. 

Connect the power cables (respect to polarity) according to the installation requirements (figure 

1

,2)

.

4. 

Place carefully the detector, so as to align the side marks and turn it clockwise all the way. 

 

Power the device and after 3-5 seconds will be ready to operate.

 

CONNECTION

1. IN-OUT -L :

 It  is  connected  to  the zone of  the  panel or  to the (

IN-OUT -L

) contact  of  the  

previous  detector.

2. OUT +R :

 It is connected to the next detector (

IN +L

)  or  if  it  is  the  last  one  to  the  terminal resistor.

3. OUT +R  and

 

-R :

 It  is  connected  with  BS-572.

4. IN +L : 

It   is   connected   to   the zone of   the   panel or   to the (

OUT +R

) contact   of   the   previous   

detector.

Mounting base

Figure

 

1.

5

5

R

+

-R

O

U

-

-L

NI

T

 +

U

R

O

N

  +

L

I

Installation procedure

2

Indication marks

921655000_23_018

Page

 1

 from

 

2

GENERAL

Before  installing  the  detector,  the  user  must 
read these instructions carefully and store this 
manual for future  reference.
The    detectors  BS-655  were  created  to  offer 
quick detection in case of fire. 
They have two parts, one plastic base which is 
installed on the ceiling and the main unit of the 
detector  which  is  fastened  to  the  base  by  a 
simple turning to the right. The detectors have 
an   indication   led which lights continuously in 
case of fire detection until there is a reset signal 
from the panel. The indication led also flashes 
every  4  sec  to indicate good operation. These 
detectors can cooperate with conventional fire 
alarm panels like BS-632 and BS-636.

OPERATION CHECK 

The operation check can be done by spraying a  
small  amount  of  smoke  into  the  detector’s 
chamber.

 

You can use the special smoke device 

A-752 of our company, or a similar device. 
It is advised to conduct a good operation test 
every  6  months  and  every  time  the  detector   
position is changed. 
It is essential to have good air circulation inside  
the detector. Therefore care must be taken so   
that the vents of the detector are not covered. 

 

 

NOTE

The detectors must be placed in the ceiling on 
visible areas with no side obstacles and away 
from sides with no air circulation or strong air 
currents  and  vapors.  Each  detector  covers 

2     

almost  50  m

and  the  distance  between  two 

detectors  must  not  exceed  15m.  Also  the 
detectors must be placed away from fluorescent 
tubes at least 

50 

cm

.

The  cables  cross  section  must  be  from

 

0.5  to

 

2

1.5mm . 

ATTENTION

!!

After the device is  installed, care must be  taken, 
so  that  the  detector  vents  are  not  blocked  by   
anything (i.e. dust, paint). Failing to do   so will 
prevent  the  smoke  particles  to  enter    the   
detection  chamber.
A f t e r  t h e  i n s t a l l a t i o n ,  i t  i s  t h e  s o l e 
responsibility  of  the  user  to  maintain  the 
detector  for  good  operation.

Certification

The  optical  smoke  detector  BS-655  is 
certified from LPCB

Also

 

LPCB controls 

the production under

 

CPR number:

 

ΚΟ

LINDROS

PIERIAS
60061 
GREECE

BS-

65

5

  

Optical smoke detector

0832

0832-

CPR-F

0

122

      

                             

   95

EN-54-

7

Connection 
with external
LED BS-572

Term

inal

resis

tor

Figure 2

Connection

You can connect up to 30 detectors BS-655 on each zone.
If the power of the detectors is turned off, wait for 3-5 seconds before you turn the power on again. 

Fr om z one

of the pa ne l

-R

O

U

-

-L

NI

T

 +

U

R

O

N

  +

L

I

-R

O

U

-

-L

NI

T

 +

U

R

O

N

  +

L

I

WARRANTY

Olympia Electronics guarantees the quality, condition and operation of the goods. The period of 
warranty is specified in the official catalogue of Olympia Electronics and also in the technical leaflet, 
which accompanies each product. This warranty ceases to exist if the buyer does not follow the 
technical instructions included in official documents given by Olympia Electronics or if the buyer 
modifies the goods provided or has any repairs or re-setting done by a third party, unless Olympia 
Electronics has fully agreed to them in writing. 

Products that have been damaged can be returned to 

the premises of our company for repair or replacement, as long as the warranty period is valid.

Olympia Electronics reserves the right to repair or to replace the returned goods and to or not 
charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to 
charge or not the buyer the transportation cost.

HEAD OFFICE

72

nd

 

km

O

.

N

.

R

Thessaloniki-Katerini

P

.

C

. 60061 

Greece

www.olympia-electronics.gr
[email protected]

Thank you for your trust in our products.  

Olympia Electronics -  European manufacturer

.

sten

a

f

1

u

n

n

e

fa t

s

Indication 

LED

Reviews: