31
9.4 Boiler Start-up and Operational Test
Verify air is purged from hydronic piping
1.
System test pumps - verify each pump is
2.
operational
Verify gas piping
3.
Confi rm pressure test. See section 7.3.
•
Visually inspect piping to determine there are no
•
open fi ttings or ends, and all valves at unused
outlets are closed and plugged/capped.
Purge air from piping
•
Check piping and connections for leaks
•
immediately after gas is turned on. Shut off
gas supply and make necessary repairs if leaks
found.
Follow OPERATING INSTRUCTIONS to initiate boiler
4.
operation. See section 10.
Inspect combustion air and vent piping. Verify pipe
5.
is not leaking and terminations are unobstructed
and vent gas discharge is not a nuisance or hazard.
Verify boiler functions.
6.
Inspect condensate disposal system. Verify
7.
condensate fl ows adequately and is disposed
properly.
Check control module operation.
8.
Check fi eld-sourced limits, low water cutoffs, etc.
9.
per manufacturer's instructions.
9.5 Check Combustion
Natural Gas
Measure input. English units*
1.
Turn off gas to all other appliances.
•
Use ½, 1 or 2 cu ft dial on gas meter. Measure
•
time required for one or more complete
revolutions. Measure time for 1-2 minutes.
Calculate input.
•
Input (MBH)
=
3600 x cu ft
seconds
Example: Gas fl ow from
Meter = 2 cu ft
Measured time = 72 seconds
Rate (MBH)
=
3600 x 2 cu ft
=
100 MBH
72 seconds
*Metric - See Glossary
** Most propane systems do not have gas fl ow meters.
9 - START UP PROCEDURE
Compare measured input to table. Adjust input rate
2.
if needed using fi gure 9-3 below.
Size
Minimum
Maximum
050
45
51
075
65
76
100
90
102
150
140
153
200
185
204
Natural Gas and Propane
Measure CO
3.
2
and compare to table. Adjust CO
2
if
needed using fi gure 9-3 below. See fi gure 9-4 for
combustion air analyzer port.
Gas
CO
2
CO
Min.
Max.
Natural Gas
8.5
9.5
<100ppm
Propane
10.0
11.0
<150ppm
NOTICE
Contact Technical Support @ 800-325-5479 for
additional information or assistance.
Natural Gas only**
Measure input. Compare to table above. Continue
4.
to measure input and CO
2
until both measured
values are within range specifi ed in tables
.
Propane Gas
Most propane systems do not have fl ow meters.
Check CO
1.
2
. Propane should be between 10% and
11.0%.
If CO
•
2
is low increase gas fl ow following fi gure
9-3.
If CO
•
2
is high decrease gas fl ow following fi gure
9-3.
To increase gas fl ow turn 'throttle' left or counter
•
clockwise
.
To decrease gas fl ow turn 'throttle' right or
•
clockwise
.
Limit adjustment to one turn and retest.
•
9-3 Gas Valve
Summary of Contents for OLSSC-075
Page 45: ...45 13 TROUBLE SHOOTING...
Page 52: ...52 14 WIRING DIAGRAM 14 1 Connection Diagram...
Page 53: ...53 14 WIRING DIAGRAM 14 2 Schematic Diagram of Ladder Form...
Page 70: ...70 NOTES...
Page 71: ...71 Date Service Performed Company Name Tech Initials Company Address Phone...
Page 72: ...ECR International Inc 2201 Dwyer Avenue Utica NY 13504 4729 web site www ecrinternational com...