8

 P/N 30149, Rev. G [12/15/2016]

13.  Humidifier

• 

Humidifier is optional accessory available through 

most heating supplies outlets. 

• 

Follow humidifier manufacturer's installation 

instructions

• Protect furnace heat exchanger from water or water 

droplets from humidifier.

• Do not use direct drive motor connections as source 

of power for 115 VAC humidifiers and humidifier 

transformers.

14.  Piping Installation

• Install fuel system in accordance with requirements 

of CAN/CSA B-139, and local regulations. 

• United States installation shall conform to NFPA No. 

31 and local codes and authorities.

• 

Use only approved fuel oil tanks, piping, fittings and 

oil filter.

• 

Install oil filter as close to burner as possible. 

• Refer to instructions and illustrations in oil burner and 

oil pump instructions shipped with the furnace.

15.  Oil Filter

Install oil filter between fuel oil storage tank and oil burner. 

When using oil burner nozzle smaller than 0.65 U.S. 

Gallons Per Hour, install additional 7 to 10 micron filter as 

close as possible to oil burner.

16.  Oil Burner Nozzles

BML and BMLV are certified for multiple firing rates, ranging 

from 59,000 to 89,000 Btu/h output. Furnace may be fired 

at ideal rate for wide range of structures by manipulating 

oil burner nozzle, flame retention head, and temperature 

rise. Refer to Table A-1 thru A-4, and furnace rating plate 

to determine proper combinations.

17.  Oil Burner Adjustment

• Adjust burner air supply to maintain fuel to air ratio 

to obtain ideal combustion conditions. 

• 

Lack of air causes "soft" and "sooty" flames, resulting 

in soot build-up throughout heat exchanger passages. 

• 

Excess combustion air causes bright roaring fire 

and high stack temperatures resulting in poor fuel 

efficiency. 

• 

BML and BMLV operate most efficiently with No. 1 

smoke spot on Bacharach Scale. Dust will eventually 

build up on air moving components of oil burner 

assembly resulting in decreased air supply with 

potential soot build up in flue gas passageways 

of heat exchanger. Soot behaves as insulator and 

impairs good heat transfer. Stack temperature 

increases, and efficiency decreases. To avoid this 

problem, adjust the air supply to provide no more 

than trace smoke spot on Bacharach Scale. 

• 

See Venting Instructions included in Vent Kits for set-

up details for sidewall vented furnaces.

NOTICE

Set up sidewall vented models to deliver zero (0) 

smoke.

NOTICE

Before operating furnace check burner alignment 

with combustion chamber. End cone of air tube must 

be centred to accommodating ring of combustion 

chamber. Adjust as necessary.

18.  Burner Electrodes

Correct positioning of electrode tips with respect to each 

other, fuel oil nozzle, and burners is essential for smooth 

light ups and proper operation. 
Refer to oil burner instructions provided with furnace 

and Appendix A Section A.2 in this manual for electrode 

specifications.

• Thermostat wiring connections are shown in wiring 

diagrams in Appendix B. Some micro-electronic 

thermostats require additional controls and wiring. 

Refer to thermostat manufacturer's instructions.

• 

Locate thermostat approximately 5 feet above floor, 

on inside wall, and where thermostat is exposed to 

average room temperatures. Avoid locations where 

thermostat is exposed to cold drafts, heat from 

nearby lamps and appliances, exposure to sunlight, 

heat from inside wall stacks, etc.

• Adjust thermostat heat anticipator to amperage 

draw of heating control circuit as measured at "R" 

and "W" terminals of thermostat. Do not measure 

current with thermostat connected to the circuit. 

Measure amperage by connecting ammeter between  

two wires which connect to thermostat "R" and "W" 

terminals.

Summary of Contents for BML-60B22

Page 1: ...BMLV Lowboy Model with ECM Series B Oil Fired Warm Air Furnaces INSTALLATION OPERATION MAINTENANCE MANUAL P N 30149 Rev G 12 15 2016 ECR International 2210 Dwyer Avenue Utica NY 13501 web site www ecr...

Page 2: ...anent Shipping Weight LB Width A Length B Height C Supply D x E Return F x G Diameter Height H BML BMLV 22 51 32 20 x 19 20 x 18 5 26 20 x 20 x1 240 LB 55 8 cm 130 8 cm 81 3 cm 52 cm x 49 cm 52 1 cm x...

Page 3: ...ation 8 15 Oil Filter 8 16 Oil Burner Nozzles 8 17 Oil Burner Adjustment 8 18 Burner Electrodes 8 19 Burner Primary Safety Control 9 20 Combustion Chamber 9 21a Circulating Air Blower BML BMLV 9 21b C...

Page 4: ...Canada HRAI or by other means prescribed or approved by the local authority having jurisdiction United States Manual J titled Load Calculation published by the Air Conditioning Contractors of America...

Page 5: ...ust have a control to prevent operation of either system unless dampers are in full heat or full cool position Air heated by the furnace shall not pass through evaporator coil unless coil is specifica...

Page 6: ...pipes sloping upward toward the chimney at a rate of one quarter inch per foot Flue pipe should not be smaller in cross sectional area than flue collar on the furnace Flue pipe should connect to chim...

Page 7: ...it control is thermally operated and automatically resets Limit control is factory installed pre set and is not adjustable If limit control opens with United Technologies 1158 120 BML electronic fan c...

Page 8: ...fficiency BML and BMLV operate most efficiently with No 1 smoke spot on Bacharach Scale Dust will eventually build up on air moving components of oil burner assembly resulting in decreased air supply...

Page 9: ...ch run and lack block ends on the trunk ducts These systems may require modification to provide some resistance to the airflow to prevent over amping of direct drive blower motor Selecting a lower blo...

Page 10: ...ow for 7 5 minutes After 7 5 minutes has elapsed motor will increase to 100 of rated airflow Used to provide dehumidification and improve system efficiency Continuous Fan Operation When thermostat con...

Page 11: ...aintenance Failure to do so could result in death or serious injury If cleaning is necessary shut off oil supply shut off power to the furnace and remove burner Use stiff brush with wire handle brush...

Page 12: ...lled in electrical power supply line to OFF 24 Operating Instructions BMLV Before Lighting 1 Open all supply and return air registers and grilles 2 Open all valves in oil pipes 3 Turn on electric powe...

Page 13: ...g 0 50 usgph F3 3 in BML 80B2 BMLV 80B2 76 000 AF76BNHS 0 65 80 A 100 psig 0 65 usgph F3 3 in BML 90B2 BMLV 90B2 85 000 AF76BNHS 0 75 80 A 100 psig 0 75 usgph F3 3 in 1 Head is shielded by ceramic ins...

Page 14: ...ieve zero smoke A 1 OIL BURNER AIR ADJUSTMENT Consult oil burner instructions provided in furnace documents envelope for specific information concerning burner adjustments operation and troubleshootin...

Page 15: ...h airflow must be increased If temperature rise is too low slow fan down 11 After air adjustments have been completed recheck the over fire draft at test port on burner mounting plate shown in Figure...

Page 16: ...obvious APPENDIX A CHECK OUT AND ADJUSTMENTS FIGURE 3 UNITED TECHNOLOGIES 1158 120 FAN TIMER BOARD BML FIGURE 4 UNITED TECHNOLOGIES 1168 1 ECM TAP BOARD BMLV Where oil shut off valve from oil storage...

Page 17: ...eed CFM External Static Pressure Inches w c 0 20 0 30 0 40 0 50 0 60 BML 60 90 100 10T DD 1 2 HP 7 1 70 F High 1722 1645 1561 1462 1375 Med High 1604 1545 1473 1383 1302 Med Low 1147 1133 1106 1063 10...

Page 18: ...ON ON D 1 5 SW3 ADJUST POS SW4 DELAY POS DIP Switch Position CFM DIP Switch Position INPUT 1 2 1 2 USGPH OFF OFF A 0 OFF OFF A 0 65 ON OFF B 15 ON OFF B 0 85 OFF ON C 15 OFF ON C 0 75 ON ON D N A ON...

Page 19: ...100 10T 3 x 2 T O 7 x 4L380 1 2 HP 3 x 7 x 4L380 1 2 HP 1 5 3 5 1 2 HP 600 1400 BML 90 100 10T 3 x 0 T O 7 x 4L380 1 2 HP 3 x 7 x 4L380 1 2 HP 1 5 3 5 1 2 HP 600 1400 Table A 11 Airflow Characteristi...

Page 20: ...20 P N 30149 Rev G 12 15 2016 APPENDIX B WIRING DIAGRAMS Chimney Vent Furnace Wiring Diagram BML BMLV...

Page 21: ...21 P N 30149 Rev G 12 15 2016 APPENDIX B WIRING DIAGRAMS Direct Vent Furnace Wiring Diagram BML BMLV...

Page 22: ...ts off burner Circulator fan is energized immediately at heat speed EFT opens the oil primary control T T connections Circulating fan runs as long as limit string stays open If there is a call for coo...

Page 23: ...ay burn out heat anticipator of standard 24 vac thermostat or cause harm to components within micro electronic thermostat Before checking oil primary control perform these preliminary checks repair or...

Page 24: ...pair light leak if necessary Open safety switch Check for open limit or auxiliary limit Check internal wiring connections loose connectors etc Furnace will not start without first pushing oil primary...

Page 25: ...l supplier Frozen oil line Gently warm oil line Insulate oil line Outdoor piping size may require increased diameter Oil burner sputtering at nozzle Electrodes out of adjustment or defective Check ele...

Page 26: ...e rise is too high speed up blower fan Defective high limit control Test high limit function of all limit switches Use duct thermometer to verify accuracy of limit control Check for obstructions to ai...

Page 27: ...12 15 2016 Model No Serial No Date Installed Contractor Contact Address Postal Code Telephone No After Hours No Fuel Supplier Fuel Oil Supplier Contact Telephone No After Hours No APPENDIX D HOMEOWNER...

Page 28: ...675 Sight Glass Cover Plate 29850 Sight Glass Gasket 2 per unit 29870 Sight Glass 29876 17 Flue Pipe Collar 27476 18 Air Filter 20 x 20 x 1 Permanent 2180032 19 Control Panel 30010 20 Control Panel Co...

Page 29: ...ng and Wheel 100 10T Belt Drive 30627 Blower Motor 1 2 HP One Speed 102000154 Motor Pulley 3 1 4 x 1 2 2240001 Blower Pulley 7 x 3 4 2240008 Belt 4L380 2240017 Blower Base 2 per unit 109005826 Grommet...

Page 30: ...er Motor 1 7 HP 3450 RPM PSC 28907 Beckett Clean cut Oil Pump A2EA6520 29688 Solid State Ignitor 28558 Oil Primary Combustion Control 7505P1530 Air Tube Combination FBX80HGXS 28561 Flame Retention Hea...

Page 31: ...31 P N 30149 Rev G 12 15 2016 Model BML and BMLV Diagram Direct Drive Model Shown 37...

Page 32: ...P N 30149 Rev G 12 15 2016 ECR International 2210 Dwyer Avenue Utica NY 13501 web site www ecrinternational com...

Reviews: