background image

30 

Static Storage Heater intelligent, 

Model 14/70_-3 

The charge control registers the outside tempera-
ture and converts this value into a control current. 
This current is passed via the control wires A1/Z1
and A2/Z2 to the control resistance in each stor-
age heater. 
At the same time, the temperature in the heater
core is also registered. The switch-off point of the
charge thermostat is therefore determined by
both the outside temperature and the tempera-
ture of the heater core. 
In this way, a control of charge according to the
outside temperature and the residual heat in the
heater is achieved, thus complying with Energy
Saving Legislation. 
The control wires can be run together with cable
feeds L, N and PE. 
Please also read the Instruction Leaflet supplied
with the Charge Control. 

Discharge
(all heaters except Model 14/691) 

As already explained in section ‘Operation’, ap-
proximately 80% of the stored heat is dissipated
into the room via convection through the three
channels made for this purpose. 
In fig.28 the front channel is shown as 

’a’

, the rear

channel as 

’b’ 

and the middle channel as

 ’c’

. The

air flow through the middle channel 

’c’ 

is controlled

by the flap 

’d’

. This flap is adjusted using the left

control element 

’f’

 on the upper right hand side of

the heater (fig. 29). It is continuously adjustable
from “0“ (fully counter-clockwise) to “max.“ (fully
clockwise). 
This discharge control enables the heat dissipation
via the air flow through the middle channel 

’c’

 to be

regulated by means of naturally boosting or thrott-
ling the convection. 
fig.27 shows the flap 

’d’

 in the closed, fig.28 in the

open position. 

Discharge can be classified in two distinct meth-
ods: 

- Manual Discharge

In position “0“ (fully counter-clockwise, start of the 
comet tail) the flap will not open at all, regardless
of the ambient conditions and the state of the
storage core. 
If an increased heat dissipation into the room is
desired, for instance at the start of the evening,
the control mechanism must have a higher set-
ting, so that the flap can open. 

- Automatic Discharge

With the control element 

’f’

 at setting “max.“ (see

fig.29), the air flap opens according to the resid-
ual heat left in the storage core. If the core is still
fully charged the flap remains closed, even if the
control element is set at “max.“. 
If the control element is adjusted to a certain set-
ting, the flap opens automatically as soon as the
corresponding level of heat dissipation has been
reached, e.g.: 

setting in middle position - the flap opens at
the beginning of the evening 

“max.“ setting, the flap opens early afternoon 

NB

: Heater 

14/691 

has no discharge control. 

Heat dissipation via convection takes place 
only in the front and rear channels (

’a’

 and 

’b’

 in fig.28). 

Commissioning 

Set charge and discharge adjusters to the “max.“
position and leave them in this position for 48
hours (i.e. 2 charging cycles). 

Due to manufacturing techniques, a part of the
heater insulation contains some binding agents
which can cause unpleasant odours during the first
charging. Any dust or machine oils which have col-
lected on the surface of, for instance, the heating
elements will also burn off, causing possible
odours. 

It is thus vitally important that the room(s) be well
ventilated during the first 48 hours or 2 charge cy-
cles!

NB:

 Model 

14/691 

has no discharge control ele-

ment. 

Summary of Contents for 14/691-3

Page 1: ...OLSBERG Instruction Manual Static Storage Heater manual 14 69_ 3 and automatic 14 69_ 4 Static Storage Heater intelligent 14 70_ 3...

Page 2: ...ly be used for the function intended Note Packaging materials replacement parts and heaters or heater parts to be scrapped must all be dis posed of correctly according to regulations Disposal of old h...

Page 3: ...is vicinity can be warmed causing natural convection The floor and or the wall must be able to take the weight of the heater Please therefore note care fully the weights given in the Technical Data se...

Page 4: ...0 130 1x0 85kW 1x1 7kW 6x SP36 14 694 4 3 4 27 2 1005x170x700 171 2x1 7kW 8x SP36 intelligent 14 702 3 1 7 13 6 565x170x700 89 1x1 7kW 4x SP36 14 703 3 2 55 20 4 785x170x700 130 1x0 85kW 1x1 7kW 6x SP...

Page 5: ...n easily tilt and fall forward If necessary lean it against the wall Open the heater Take off the plastic covering caps left and right Remove the screws fig 7 Pull the front panel at the bottom 10cm o...

Page 6: ...spacers 50mm long The clearance spacers are in the packaging and can be slipped over the fixing screw The length of spacer chosen depends on the necessary clear ance to the wall fig 13 For skirting bo...

Page 7: ...he lower right of the plinth fig 16a Static Storage Heater intelligent 14 70_ 3 On Peak Supply A1 Z1 und A2 Z2 Feed the electrical cable 3x1 5mm through the left conduit in the heater base and then fo...

Page 8: ...For heaters with 3 or 4 bricks in a row put the outside bricks in first fig 19 Build up the complete rear brick columns Reinstall the heater elements fig 20 Make sure that the element connection tabs...

Page 9: ...full left CLOSED fig 24 to full right OPEN fig 25 and back fig 24 fig 25 Close the heater fig 26 Firmly fix the side panels to the upper right and left side inner cabinet using the screws Set the fron...

Page 10: ...nor spray tubes or similar objects closer than 25cm in front of or on the heater especially not in front of the air outlet grille It is important to remember that the surfaces of the heater can reach...

Page 11: ...panel which should act as a reminder Major components Storage core 1 The storage core bricks are made of a refractory material which can reach a temperature of more than 700 C at full heater charge He...

Page 12: ...ter charge up to 90 in relation to the room temperature The other 10 is influ enced by the temperature of the storage core The room temperature sensor is mounted inside the front right of the heater c...

Page 13: ...shows the flap d in the closed fig 28 in the open position Discharge can be classified in two distinct meth ods Manual Discharge In position 0 fully counter clockwise start of the comet tail the flap...

Page 14: ...off the adjustment knobs fig 30 Remove the front retaining screws left and right fig 30 and fig 31 Pull the control unit forward and out fig 32 and fig 33 Refitting takes place in the opposite manner...

Page 15: ...32 Circuit diagram manual 14 691 3 14 692 3 14 693 3 14 694 3 14 695 3 2 78 4514 4923...

Page 16: ...33 automatic 14 692 4 14 693 4 14 694 4 14 696 4 2 78 4514 4924...

Page 17: ...34 intelligent 14 702 3 14 703 3 14 704 3 1 78 4514 7023...

Page 18: ...84 10 78 4614 6913 02 2011 Olsberg GmbH H ttenstra e 38 59939 Olsberg T 49 2962 805 0 F 49 2962 805 180 info olsberg com olsberg com...

Reviews: