The Sensor Setup Tab
18
Select the sensor channels option to set the number of active channels
The Sensor FIND Function
The sensor FIND function is used during initial set up of the system to test that all connected
detectors communicate to the control panel. The function can also be used to automatically install
onto the panel all of the detectors which are 'found'. By doing this channels are automatically set
up on the controller for the Address, Cable, Range, Gas Type etc. This will speed channel set up
but it should be noted that performing a FIND and auto install will erase all the existing set up
information including alarm levels and alarm action types.
Select the start and end adress to
search between.
Select the cable numbers to search
Select FIND to start searching for
detectors.
The display will show how
many detectors were found, on
which cables and indicates the
first address found on the
cable
The display now indicates
how many sensors have
been found.
At this stage this may just
be useful diagnostic
information in which case
select ABORT to exit the
sensor FIND or....
Select NEXT to continue
and automatically install
sensors onto the system