Olimpia splendid INVERTER 12 HP Service Manual Download Page 8

 

 

7.

 

RATING MODE 

 
In cooling mode should be set by remote control, the speed of the fan and internal temperature of 18°C; then press 
for 6 times the button on the remote night (T3). After 2 consecutive beeps the compressor will start to operate at a 
frequency of 43 Hz. Will be activated so that the two fans work at full speed. 
To end the procedure, press standby button or automatically cease after 5 hours from setting. The same goes for 
the  heating  mode,  the  only  difference  is  to  set  a  temperature  of  30°C  corresponding  to  an  operating  frequency 
compressor 50Hz. 
 

8.

 

DIAGNOSTIC ALARMS 

 

All alarms are reported in table. They reset automatically after 3 minutes after the alert or, alternatively, you can 
turn off the machine and wait just 30 seconds. ONLY for IPM alarms, if they are activated more than 4 times by 15 
minutes, the rehabilitation automatic function is turned off. Both types of alarm functions do not require as self-
diagnosis because are displayed in real time. 

 

 

 
 
 
 
 
 
 
 
 
 

DIAGNOSTIC ALARMS  CONTROL MODULE 

(blinking on display) 

Tripping threshold 

LED D 

(green) 

LED C 

(yellow) 

LED B 

(green) 

LED A 

(red) 

T° room sensor fault 

(open/short circuit) 

 

 

T° int. heat-exchanger sensor fault 

(open/short circuit) 

 

 

Internal heat-exchanger temperature too 
low 

(LT

-2°C / 7°C 

 

 

Internal heat-exchanger temperature too 
high 

(HTI)

 

65°C / 42°C 

 

 

IDU IPM comunication error 

 

 

IDU AC fan motor no speed feedback 

 

 

Condensate tank MAX LEVEL alarm

(OF)

 

 

 

 

EEprom reading error 

 

 

DIAGNOSTIC ALARMS IPM MODULE 

(blinking on display) 

Tripping threshold 

LED D 

(green) 

LED C 

(yellow) 

LED B 

(green) 

LED A 

(red) 

T°ext. sensor fault 

(open/short circuit) 

 

 

T°ext. heat-exchanger sensor fault 

(open/short circuit) 

 

 

T°discharge sensor fault 

(open/short circuit) 

 

 

DC compressor feedback 

 

 

Outdoor unit comunication error 

 

 

Over current 

 

 

Compressor output No load 

 

 

Over/under DC voltage 

380V DC/240V DC 

 

 

DC compressor start failure 

 

 

External heat-exchanger temperature too 
high

(HTE)

 

70°C / 60°C 

 

 

IPM protection 

 

 

EEPROM reading error 

 

 

EEPROM writing error 

 

 

Discharge temperature too high 

110°C/-- 

 

 

AC zero crossing detection fault 

 

 

Summary of Contents for INVERTER 12 HP

Page 1: ...y Efficiency Class in cooling mode A A A A Energy Efficiency Class in heating mode _ A _ A Fan speed indoor outdoor 3 4 3 4 3 4 3 4 Room air volume in cooling mode max med min m h 490 430 360 490 430...

Page 2: ...ilters the machine doesn t stop it is reset by pressing the micro button for a few seconds 3 REMOTE CONTROL T1 ON OFF standby T2 Economy key T3 Night key T4 Operating mode selector T5 Fan speed select...

Page 3: ...minute When time ends the compressor continues to work in according to procedure described below frequency is recalculated every 3 minutes T room T set 3 C MAXIMUM frequency T set 3 C T room T set 1 C...

Page 4: ...Hz and then work at least for 28 sec after which the outdoor fan is turned off After another 2 sec also 4 ways valve is disabled so the compressor increases the frequency to the limit of 60 Hz The def...

Page 5: ...um speed and the T set is automatically increased by 1 C after 1 hour and by a further 1 C after 2 hours In heating mode when the night mode is enabled the internal fan is forced to minimum speed exte...

Page 6: ...2 minutes after that the limit was overtaken In case of air conditioner is turned on with T discharge on the limit compressor starts to work The frequency is limited to the first compressor frequency...

Page 7: ...n T camb amounted to 3 C it is not possible to separate two operations Figure 1 refers to a machine configured for installation near the floor in which air flows upwards The same configuration may als...

Page 8: ...in real time DIAGNOSTIC ALARMS CONTROL MODULE blinking on display Tripping threshold LED D green LED C yellow LED B green LED A red T room sensor fault open short circuit 0 1 T int heat exchanger sen...

Page 9: ...side the machine Excessive dirt accumulated on the indoor heat exchanger Malfunction IDU fan Low external air temperature 8 4 Internal heat exchanger temperature too high HTI The HTI alarm occurs when...

Page 10: ...10 SCHEMATIC...

Page 11: ...9 1 Control board side...

Page 12: ...9 2 IPM board side...

Page 13: ...11 OHMICH VALUES COMPRESSOR DISCHARGE SENSOR...

Page 14: ...12 OHMICH LVALUES HEAT EXCHANGER AND AIR SENSOR...

Page 15: ...13 ACCESSORIES Currently there aren t accessories except those supplied with the machine...