by means of B4/B5 or SW4/SW5 (if a Tset higher than 27°C was previously selected in 
cooling, when the heating mode is selected the Tset must be automatically set to 21°C), 
 and its value is shown both on remote and local interfaces (by D1, D2, and S1+S2=’°C’). 
Once heating mode is selected, if Troom 

 Tset nothing happens (all outputs remain switched off). 

If  Troom 

  Tset-Hy  and  Res_time  seconds  from  previous  compressor  shutdown  are  elapsed,  the  4-way 

valve is activated first, then compressor and external fan can be switched ON. 
As soon as Troom 

 Tset the compressor and external fan are switched OFF (the 4 way valve must remain 

energized).  
Next  time  the  condition  Troom 

  Tset-Hy  occurs,  provided  that  Res_time  seconds  from  previous 

compressor shutdown are elapsed, compressor and external fan can be switched ON again. 

 

Internal fan it’s switched to low speed for t_lowspeed seconds from each compressor start time (regardless 
of  any  speed  selection),  then  it  can  be  switched  to  actual  selected  speed.  Each  time  the  compressor  is 
switched  OFF  (due  to  Troom 

  Tset  or  unit  to  Stby  mode),  the  internal  fan  is  set  to  low  speed  for 

t_lowspeed seconds and then it’s switched OFF. 
Here are the details about the available fan speeds: 

 

 

High FAN 

Med FAN 

Min FAN 

HEATING 

MODE 

1280 r/min ±5% 

1100 r/min ±5% 

920 r/min ±5% 

 

When auto fan speed is selected (only from the remote control by pressing B7), the actual speed is selected 
depending on room temperature and Tset as following (only when the compressor is ON, otherwise the int 
fan keeps OFF): 

 

Tset – 3°C < Troom 

 Tset: minimum speed is enabled; 

 

Tset – 6° < Troom 

 Tset-3°C: medium speed is enabled; 

 

Troom 

 Tset-6°C: maximum speed is enabled. 

 

At  least  3  minutes  must  elapse  between  one  automatic  speed  change  and  another  (if  Tset  or  fan  speed 
selection is changed, the new speed is enabled without any delay). 

The display L1 shows the auto fan mode by cyclically switching the fan speed symbols as follows: 
 
 
 
 

  

     

 

 

 

      …… 

 
 

The heating defrost subprogram starts when Troom 

 Tdefrost and ends when Troom > Tdefrost +2°C, 

and forces the compressor to periodically switch OFF and switch ON for t_defrost_off minutes (OFF state 
duration) and t_defrost_on minutes (ON state duration) respectively. 
When  the  heating  defrost  function  is  active,  the  internal  fan  behaves  as  usual  in  heating  (each  time  the 
compressor is switched ON, it’s set to low speed for t_lowspeed seconds first then to the selected fan speed; 
each  time  the  compressor  is  switched  OFF,  it’s  set  to  low  speed  for  t_lowspeed  seconds  first,  then  it’s 
switched OFF). 
 
 

Summary of Contents for ELLISSE HP

Page 1: ...ELLISSE HP 1 Technical Specification ...

Page 2: ...t decrease SW6 Unit switch ON OFF delay confirmation cancel L1 LCD with blue backlight L2 Standby mode LED red 2 1 Control Board Display D1 Tset Timer tens D2 Tset Timer units DP Decimal point S1 Time indicator S2 Temperature indicator S3 Delayed switch ON S4 Timer mode S5 Delayed switch OFF S6 Cooling mode S7 Dehumidification mode S8 Automatic mode S9 Sleep mode S10 Fan mode low fan speed S11 Med...

Page 3: ...3 Remote control 3 1 Remote control display ...

Page 4: ...n a speed feedback signal provided by the fan motor itself see the motor specs in enclosure 6 The target speed is compared to the feedback signal and the motor voltage is continuously adjusted in order to minimize the speed values difference Here are the details about the available fan speeds High FAN Med FAN Min FAN FAN MODE 1280 r min 5 1100 r min 5 920 r min 5 LCD symbols displayed In fan mode ...

Page 5: ...urs The cooling defrosting subprogram which starts with Troom Tmin and finishes with Troom Tmin 2 C forces the compressor and ext fan and water disposal motor outputs to periodically switch OFF and switch ON for Tp_off minutes OFF state duration and Tp_on minutes ON state duration respectively When the defrosting function is active the internal fan speed must be set as follows Fan speed setting In...

Page 6: ...rking cycle which is controlled as follows o ON continuously for Troom Tset 2 C o 6 minutes ON and 6 minutes OFF for Tset 2 C Troom Tset 2 C o 6 minutes ON and 12 minutes OFF for Tset 4 C Troom Tset 2 C o OFF continuously for Troom Tset 4 C Note After each dehumi mode start the compressor always waits 3 minutes before its first activation Regardless of Troom and Tset acquired compressor always run...

Page 7: ...tched OFF Here are the details about the available fan speeds High FAN Med FAN Min FAN HEATING MODE 1280 r min 5 1100 r min 5 920 r min 5 When auto fan speed is selected only from the remote control by pressing B7 the actual speed is selected depending on room temperature and Tset as following only when the compressor is ON otherwise the int fan keeps OFF Tset 3 C Troom Tset minimum speed is enabl...

Page 8: ...is placed in Stand by or when the power supply is disconnected in all these situations the function timer is reset and Tset restored to the last one received from remote controller In this status too all appliance s malfunctions are enabled 10 AUTOMATIC MODE This mode can be selected by pressing B2 or SW2 until the automatic symbol is shown on both the remote control s and L1 displays In this mode...

Page 9: ...d L2 ON When the delay time set has elapsed the unit switches ON with latest selected settings All the timer symbols on both the remote controller and the local interface disappear 12 2 Timer OFF setting from remote control o With the unit in any working mode except standby press B9 to set the desired time delay from 1 to 12 hours after which the unit will switch OFF starting from timer confirmati...

Page 10: ...unit will switch to standby mode L1 OFF and L2 ON o When the delay time set has elapsed the unit switches ON with previously selected settings All the timer symbols S2 S3 and S4 on the local interface disappear 12 4 Timer OFF setting from the display unit o With the unit in any working mode except standby press SW6 to set the desired time delay from 1 to 12 hours after which the unit will switch O...

Page 11: ...by remote controller nor by display unit and the relative alarm code see table below is shown on display unit LCD Once the correct probe operation is restored the unit is placed in Standby mode 13 3 Internal fan alarm When fan speed feedback acquired keeps lower than 400 rpm for 20 seconds in all the working situation when the fan should operate the appliance stops to run all outputs are switched ...

Page 12: ...y valve indoor fan max speed and outdoor fan work regardless Troom In Diagnostic mode all the alarms are enabled Defrost and Heatmax functions for Heating mode Defrost function for Cooling mode are enabled In Diagnostic mode by pressing the SW6 button the room temperature acquired by the probe is shown on D1 and D2 Press the standby key SW1 or disconnect the power supply to quit Diagnostic mode 15...

Page 13: ...15 Wiring diagram ...

Page 14: ...16 Sensor data ...

Page 15: ......

Reviews: