29. CHARGING PROCEDURES
In addition to conventional charging procedures, the following requirements
shall be followed.
Ensure that contamination of different refrigerants does not occur when using
charging equipment. Hoses or lines shall be as short as possible to minimise
the amount of refrigerant contained in them.
Cylinders shall be kept upright.
Ensure that the refrigeration system is earthed prior to charging the system
with refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigeration system. Prior to
recharging the system it shall be pressure tested with OFN.
The system shall be leak tested on completion of charging but prior to
commissioning. A follow up leak test shall be carried out prior to leaving the
site.
30. DECOMMISSIONING
Before carrying out this procedure, it is essential that the technician is
completely familiar with the equipment and all its detail. It is recommended
good practice that all refrigerants are recovered safely.
Prior to the task being carried out, an oil and refrigerant sample shall be
taken in case analysis is required prior to re-use of reclaimed refrigerant. It is
essential that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:
• Mechanical handling equipment is available, if required, for handling
refrigerant cylinders;
• All personal protective equipment is available and being used
correctly;
• The recovery process is supervised at all times by a competent person;
• Recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be
removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes
place.
g) Start the recovery machine and operate in accordance with manufacturer’s
instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even
temporarily.
j) When the cylinders have been filled correctly and the process completed,
make sure that the cylinders and the equipment are removed from site
promptly and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration
system unless it has been cleaned and checked.
Summary of Contents for DOLCECLIMA ARIA 8
Page 2: ......
Page 8: ...min 2m min 2m 2 1 5 5 2 26 4 4 B A 6 8 10 7 9 11...
Page 9: ...24 24a 24 24a 40 C 23 23 17 16 23 15 18 28 7 13 14 7 28 12...
Page 194: ...EL 2 A T x x o o o o A x x EE 4 24 4 1 24 4 1 a 24 4 1 b 24 4 1 c 25 4 2 25 4 2 a 25 5 25 6 26...
Page 195: ...DOLCECLIMA ARIA 8 EL 3 0 0 1 0 2 0 2 1 Service SERVICE...
Page 196: ...EL 4...
Page 197: ...DOLCECLIMA ARIA 8 EL 5 0 3 3 1 OL PIA SPLENDID 2 3 4 5 6 7 8 9...
Page 198: ...EL 6 10 11 OLIMPIA SPLENDID 12 13 14 15 16 17 18 19 20 2 20 21 A...
Page 199: ...DOLCECLIMA ARIA 8 EL 7 22 23 24 25 26 27 28 3 29 3 30 31 50 50 1 32 4 33 34 35 36 37 38 39 40...
Page 200: ...EL 8 41 42 43 44 2 dvd player 6 45 46 47 48 49 50 51 52 53 20 30...
Page 201: ...DOLCECLIMA ARIA 8 EL 9 0 4 X OLIMPIA SPLENDID 0 5 1 1...
Page 203: ...DOLCECLIMA ARIA 8 EL 11 12 13 14 15 16 17 18 19 20 21 22 a b c...
Page 204: ...EL 12 d e CO2 f g h...
Page 205: ...DOLCECLIMA ARIA 8 EL 13 I 23 a b 24...
Page 206: ...EL 14 25 26 27 25 OFN 28 OFN OFN OFN OFN...
Page 207: ...DOLCECLIMA ARIA 8 EL 15 29 OFN 30 a b c d e f g h 80 i...
Page 208: ...EL 16 j k 31 32...
Page 210: ...EL 18 2 2 1 4 2 a SS 2 2 a b c 7 d 30 cm 1 e f g h i...
Page 213: ...DOLCECLIMA ARIA 8 EL 21 3 3 TV 3 3 a a 14 b 14 c 3 3 b 1 5V AAA 14...
Page 216: ...EL 24 4 4 1 4 1 a a b 4 1 b 15 a b 23 c 23 40 d 23 e 23 f 23 g 16 23...
Page 218: ...EL 26 6 LED S9 2 1...
Page 219: ......
Page 220: ...264177C...