27
2.7
Connecting the Detector
This section describes how to connect the electric cabling to the detector (Figure 7).
Ø
To connect the detector to the electrical cables
15
Disconnect the power.
16
Remove the back cover of the detector by removing four (4) socket head-screws in the
cover bolts. The terminal chamber is now revealed.
17
Remove the protective plug mounted on the Detector Conduit/Cable entry; pull the
wires through the Detector Inlet.
18
Use a ¾" – 14 NPT explosion-proof conduit connection or M25x1.5 flameproof gland
to assemble the cable / conduit to the detector.
Figure 7: Detector with Cover Removed
19
Connect the wires to the required terminals on the Terminal Board according to the
wiring diagram (Figure 7) and Table 17.
20
Connect the grounding (earth) wire to the ground (earth) screw outside the detector
(Earth Terminal). The detector must be well grounded to earth ground.
21
Verify the wiring. Improper wiring may damage the detector.
22
Check the wires for secure mechanical connection and press them neatly against the
terminal to prevent them from interfering while closing the back cover (Figure 7).
23
Place and secure the detector’s back cover by screwing the four (4) socket-head-
screws in the Cover Bolts (Figure 4).
Earth
Terminal
Terminal
Chamber
Terminals
Internal Earth
Terminal
Detector Holding
Screw
Conduit / Cable
Inlet