OLCT 10N
User Manual
CO
2
MX 43 with Rev. A or Rev. B mother board
Distance in meters
Line cross-section
Number of OLCT 10N detectors used to
detect CO
2
0.75 mm²
(AWG 18)
0.5 mm²
(AWG 20)
0.22 mm²
(AWG 24)
1
1000
1000
1000
2
1000
1000
500
5
1000
600
250
10
550
300
125
12
450
250
100
Above 12
Maximum load for an MX 43 line (>500mA).
An external supply must be used
MX 43 with Rev. C mother board
Distance in meters
Line cross-section
Number of OLCT 10N detectors used to
detect CO
2
)
0.75 mm²
(AWG 18)
0.5 mm²
(AWG 20)
0.22 mm²
(AWG 24)
1
1000
1000
1000
2
1000
1000
500
5
1000
600
250
10
550
300
125
20
250
150
60
30
180
100
40
Above 30
Maximum load for an MX 43 line (>1200mA).
An external supply must be used