25
3.3.4.
Fault thresholds
Processing of detector faults
Each channel detects the following faults.
For toxic and explosive gas detectors:
-
line interrupted (0 mA),
-
line short-circuited or excessive consumption,
-
negative offset (more than 20% of measuring scale),
-
line in calibration mode (2 mA) (if confirmed by programming).
For detectors of the explosive gas type (4-20 mA and 340 mA) in normal mode and if the
measurement is greater than 100% of the measuring scale, there are the following immediate
results:
-
Display: SUP
-
The relays are actuated if the thresholds are reached.
-
The general fault relay is actuated.
-
The 4-20 mA output of the channel is greater than 20 mA.
-
ALl these states are memorized and the only way of acknowledging them is to
switch off the channel and then restart it.
Faults are valid after a preprogrammed time (in the same way as alarms).
FAULT BLOCK DIAGRAM
END
START
Wait until the fault has been present
for at least 5 seconds.
The relays are locked in their current state.
The common fault relay is engaged.
The buzzer is engaged.
The channel fault LED is illuminated. *
1 mA is sent on the 4-20 mA output.
* The LED is extinguished as soon a the fault disappears.
Summary of Contents for MX 52
Page 4: ...4 ...
Page 44: ...44 ...
Page 56: ...56 ...
Page 57: ...57 7 7 V VI IE EW WS S S SP PE EC CI IF FI IE ED D I IN N T TH HE E M MA AN NU UA AL L ...
Page 58: ...58 ...
Page 59: ...59 ...
Page 60: ...60 ...
Page 61: ...61 ...
Page 62: ...62 ...
Page 63: ...63 ...
Page 64: ...64 ...
Page 65: ...65 ...
Page 66: ...66 ...
Page 67: ...67 ...
Page 68: ...68 2 ...
Page 69: ...69 ...
Page 70: ...70 ...
Page 71: ...71 ...
Page 72: ...72 ...
Page 73: ...73 ...
Page 74: ...74 ...
Page 75: ...75 ...
Page 76: ...76 ...
Page 77: ...77 ...
Page 78: ...78 ...
Page 79: ...79 ...
Page 80: ...80 ...
Page 81: ...81 ...
Page 82: ...82 ...
Page 83: ...83 ...
Page 84: ...84 ...
Page 85: ...85 ...
Page 86: ...86 ...
Page 92: ...92 ...
Page 93: ...93 ...
Page 94: ...94 ...
Page 95: ......