- 9 -
1.3.2. 3-wire detectors 4-20 mA: 3 connecting wires for shielded cable
-
Resistance of detector / unit cable: 16 ohms maximum per wire, i.e. 32 ohms in
loop (1 km for cable 3 x 1.5 mm²).
-
Connection on MX52 unit: see Fig. 10.
1.3.3. 2-wire detectors 4-20 mA: 2 connecting wires for shielded cable
-
Resistance of detector / unit cable: 32 ohms maximum per wire, i.e. 64 ohms in
loop (2 km for cable 2 x 1.5 mm²).
-
Connection on MX52 unit: see Fig. 11.
1.3.4. FIRE detectors: 2 connecting wires for shielded cable
The current commercial designations are as follows:
-
“Thermovelo” detectors of type EC 11 (sensitive to temperature variations)
-
Ionic detectors of type EI 1 100 (sensitive to smoke)
-
Optical detectors of type EO 1 100 (sensitive to smoke)
-
Resistance of detector / unit cable: 28 ohms maximum per wire, i.e. 56 ohms in
loop (2 km for cable 2 x 1.5 mm²)
-
Fire detectors can be detected in parallel to a maximum of five. The end-of-loop
resistor (2.7 K) is to be placed at the end of the line on the last detector.
-
Connection on MX52 unit: see Fig. 11
1.3.5. FLAME detectors: 2, 3 or 4 connecting wires for shielded cable
depending on utilization
REMARK
The detectors can be supplied with power either via the MX52 unit or by an auxiliary 24 V
DC source.
These detectors can operate in standalone mode:
24 V DC power supply and direct utilization of relay contacts in accordance with the technical
specification corresponding to the detector used.
Summary of Contents for MX 52
Page 4: ... 4 ...
Page 18: ... 18 ...
Page 22: ... 22 ...
Page 26: ... 26 ...
Page 27: ... 27 ...
Page 28: ... 28 ...
Page 29: ... 29 6 6 V Vi ie ew ws s d de ep pi ic ct te ed d i in n t th he e l le ea af fl le et t ...
Page 30: ... 30 MX52 OVERALL DIMENSIONS FIGURE 1 ...
Page 33: ... 33 B MICRO BOARD FIGURE 6 A ...
Page 47: ......