Small air oil coolers are equipped with a single phase or

three phase outer-rotor motor. 
Larger  air  oil  coolers  are  equipped  with  a  standard  three
phase asynchronous inner rotor motor according to 
IEC 60072 and IEC 60034.

Normal ambient temperature for the electric motor: 

-20 °C - +40 °C.  Connect the electrical motor to the electri-
city  supply  system  according  to  Electrical  connection. 

See

the rating plate for further information.

The electric motor on large air oil coolers is equipped with
a motor bracket.

The air oil cooler can be provided with a thermo contact.

The fan will then start automatically when the preset tem-
perature has been reached.

The  acoustic  pressure  level  could  reach  50-92  LpA  dB(A)

at 1 m distance normal operating conditions. Inappropriate
locatation,  or  operation  under  extreme  conditions,  could
generate  increase  in  acoustic  pressure  level  and  reduced
cooling capacity. 

For general operating data, see Technical data.

Identification plate

The identification plate is fitted on the fan housing. 

See Figure 2.

The identification  plate contains the following information:

A

- Part number

B

- Designation

C

- Serial number

D

- Date of delivery (year and week, e.g. 1018, i.e. year

2010 and week 18).

Replace a damaged or missing type plate as soon as possible.

Installation

Lifting

Caution

Risk of bodily injury. To prevent physical harm 

when lifting the unit, ensure correct lifting technique.

Make sure that all lifting devices are free from damage and
approved for the weight of the air oil cooler.

Air oil coolers as from size 033 are prepared for installation

of  lifting  eyes.  Lifting  eyes  are  available  from  Olaer  on
request.

Mounting

Precaution

Risk of bodily harm. Make sure that the 

air oil cooler is securely fixed.

The air oil cooler can be mounted in any position. However,

an upright installation standing on its feet is recommended.

A  free  space  corresponding  to  a  minimum  of  half  the

height of the matrix (A) should be available in front of and
behind the air oil cooler to allow for good air flow, i.e. opti-
mal cooling capacity as well as low acoustic pressure level. 

See Figure 3.

Inappropriate  location  of  the  air  oil  cooler  or  operation

under extreme conditions could generate increased acoustic
pressure level and reduce cooling capacity. 

Connection of cooler matrix

Connect  the  cooler  matrix  using  flexible  hydraulic  hoses
both to and from the cooler. Make sure that all connections
and hoses are sized according to the system pressure, flow,
temperature and fluid.

Connect the cooler matrix as illustrated below. 

See Figure 4 or Figure 5.

A

- Inlet.

B

- Outlet for single-pass.

C

- Outlet for two-pass.

D

- Thermo contact connection.

Dimensions on connections are cooler matrix size dependent.
Connection chart, 

see Figure 6.

Important

The cooler matrix is designed for maximum dyna-

mic working pressure 14 bar. When the cooler is installed in a
return line, there should be no pressure spikes. If this is not
possible, an offline cooling system should be used.

Electrical connection

Danger

Risk of electrical shock. All electrical connec-

tions must be made by a qualified electrician!

Prior  to  connecting  the  motor  to  the  electricity  supply

system, make sure the information on the motor label corre-
sponds to the line voltage and frequency. The motor should
be installed according to general and electrical safety
rules and should be made by a qualified electrician.

Precaution

Be careful when connecting. Improperly 

made connections, damaged cables, etc. could cause

components to become live or result in the incorrect direc-
tion of rotation of the electric motor.

•  Connection of a single phase outer rotor motor: 

Connect the live to L 

(blue)

, neutral to N

(black) 

and ground to PE 

(yellow/green)

See Figure 7.

• Connection of three phase outer rotor motor. 

See Figure 8 or Figure 9.

• Connection of three phase inner rotor motor. 

See Figure 10. 

Example for motor: 220-240 V D/380-420 V Y.

The direction of rotation of three phase motors is altered

by changing connection of two phases.

If the cooler is fitted with a thermo contact, use a relay if

the current load exceeds the maximum load for the thermo
contact.

Note! 

A motor overload protection is recommended.

The  size  of  the  overload  protection/fuse,  depends  on  fan
size and air flow across the cooler. Contact Olaer concerning
motor protection/fuse size.

8

OLAER LAC AIR OIL COOLER  |

Installation and servicing manual  |  English

Summary of Contents for LAC

Page 1: ...The Professional Choice www olaer com LAC With AC motor optimized for industrial use Installation and servicing manual SE GB DE FR ES...

Page 2: ...Brown Braun Marron Maron U1 Svart Black Schwarz Noir Negro U2 Gr n Green Gru n Vert Verde V1 Bl Blue Blau Bleu Azul V2 Vit White Wei Blanc Blanco W1 Brun Brown Braun Marron Maron W2 Gul Yellow Gelb J...

Page 3: ...AIR OIL COOLER LAC OLAER LAC AIR OIL COOLER Installation and servicing manual The Professional Choice 1 2 A B C D 3 5 6 1 2 A 1 2 A A A A C D D B B AIR OIL COOLER LAC LAC 4...

Page 4: ...AIR OIL COOL ER LAC LAC 12 11 The Professional Choice OLAER LAC AIR OIL COOLER Installation and servicing manual 14 13 15 A 15 B 16 17 AIR OIL COOLER LAC LAC AIR OIL COOLER LAC...

Page 5: ...L ftereinheit F Motorhalterung G Schutzgitter H Elektromotor I Luftereinheit mit Motor Die Ausfuhrung mit starrer oder loser Nabe h ngt vom K hlermodell ab Liste des composants A Radiateur B Bouchons...

Page 6: ...Bypassventil Einzeldurchlauf D T Bypassventil Doppeldurchlauf E Termokontakt Mit Drucksteuerung oder Temperatur und Drucksteuerung lieferbar Zubeh r F Hebe sen G Vibrationsd mpfer quipements en optio...

Page 7: ...lation 13 Bedienung 14 Vorbeugende Wartung 14 Wartung 15 Technische Daten 16 bereinstimmungserkl rung 17 Introduction 18 Consignes de s curit 18 Description 19 Installation 19 Consignes d emploi 20 En...

Page 8: ...ormation Till ggsinformation markeras enligt f ljande Anm Anger extra information som kan underl tta f rst else f r eller utf rande av ett visst moment vergripande f reskrifter Lyft Varning Kl m kross...

Page 9: ...hydraulslangar b de till och fr n kylelementet Se till att kopplingar och slangar r dimensionerade efter sys temets tryck fl de temperatur och olja Anslut hydraul slangar till kylelementet enligt f lj...

Page 10: ...nt smuts f rs mrar kyleffekten luftoljekylaren r fri fr n skador byt ut trasiga kompo nenter luftoljekylaren inte l cker tg rda eventuellt l ckage varningsdekal r i gott skick ers tt skadad eller sakn...

Page 11: ...i motorkonsolen 2 Skruva fast motorn i motorf stet Se Bild 16 3 Passa in sp ret i navet mot krysskilen p motorn Anv nd etanol i navet som sm rjning och tryck fast fl kten med nav p motoraxeln Knacka e...

Page 12: ...hazard zones being reached by upper and lower limbs SS EN ISO 13857 2008 Electric motors used on the product comply with the Low Voltage Directive LVD 73 23 EEC of 19 February 1973 modified by Direct...

Page 13: ...dditional information Additional information is marked as follows Note This alerts you to important information related to the text in a paragraph Overall instructions Lifting Caution Risk of bodily i...

Page 14: ...See Figure 3 Inappropriate location of the air oil cooler or operation under extreme conditions could generate increased acoustic pressure level and reduce cooling capacity Connection of cooler matrix...

Page 15: ...rried out at regular intervals Make sure that there is no abnormal noise or vibrations that air oil cooler is securely fixed that the cooler matrix is clean debris will reduce the cooling capacity tha...

Page 16: ...ether with the hub as from size LAC 033 1 If the air oil cooler is fitted with motor bracket fit the motor to the motor bracket 2 Secure the electric motor to the motor attachment See Figure 16 3 Fit...

Page 17: ...ety distances to prevent hazard zones being reached by upper and lower limbs SS EN ISO 13857 2008 Electric motors used on the product comply with the Low Voltage Directive LVD 73 23 EEC of 19 February...

Page 18: ...werden Ein solcher Unfall kann zu Verletzungen f hren und sonstigen Sicherheit Hinweistexte zur sonstigen Sicherheit Gegenst nde Prozesse oder Umfeld und Bedienung sind wie folgt unter teilt Wichtig...

Page 19: ...use Siehe Abb 2 Das Typenschild enth lt Angaben zu A Artikelnummer B Artikelbezeichnung C Seriennummer D Lieferdatum Jahr und Kalenderwoche z B 1018 also Jahr 2010 und KW 18 Ein besch digtes oder feh...

Page 20: ...g Vor dem ersten Start Vorsicht Verletzungsgefahr berpr fen ob der l Luftk hler ordnungsgem angeschlossen und befestigt ist Olaer empfiehlt folgende Vorgehensweise vor der Inbetriebnahme des l Luftk h...

Page 21: ...gefahr Im Betrieb kann der l Luftk hler sehr hei werden Daher sollte er erst ber hrt werden wenn er sich abgek hlt hat Warnung Verletzungsgefahr Vor Wartungsarbeiten den Motorantrieb abschalten 1 Anla...

Page 22: ...alterung am L ftergeh use anschrauben Siehe Abb 13 Eine eventuell vorhandene Motorkonsole anschrauben 7 berpr fen ob das L fterrad zentriert ist und sich frei dreht mit der Hand drehen Bei Bedarf die...

Page 23: ...die von den oberen und unteren Gliedma en erreciht werden SS EN ISO 13857 2008 Die im Produkt verwendete Elektromotoren sind in bereinstimmung mit der Niederspannungsrichtlinie 73 23 EWG vom 19 Febru...

Page 24: ...biens proc d ou environnement et la manipulation de l changeur sont class s comme suit Important indique qu un accident peut se produire en cas de nonrespect de la consigne Cet accident peut entra ne...

Page 25: ...rence du produit B La d signation du produit C Le num ro de s rie D La date de livraison ann e et semaine par ex 1018 c est dire l ann e 2010 et la semaine 18 Remplacer imm diatement une plaque endom...

Page 26: ...ur 1 Effectuer un cycle de fonctionnement utilisant le m me fluide que celui utilis dans le syst me 2 Le fluide doit tre filtr avant son passage dans l changeur Pour les combinaisons recommand es de f...

Page 27: ...sser les vis avec rondelles qui fixent le radiateur au caisson Voir Figure 12 7 D poser le radiateur Montage du radiateur 1 Mettre en place le radiateur 2 Fixer le radiateur au caisson avec les vis Vo...

Page 28: ...Connecter la source d entra nement du moteur 10 Effectuer les proc dures selon Avant le d marrage et Lors du d marrage Caract ristiques techniques Radiateur Pression statique de service maximale 21 b...

Page 29: ...es machines Distances de s curit pour emp cher l atteinte des zones dangereuses par les membres sup rieurs et inf rieurs SS EN ISO 13857 2008 Les moteurs lectriques utilis s sur le produit sont confor...

Page 30: ...seguridad concernientes a otros aspectos de seguridad propiedad proceso medio ambiente y a la mani pulaci n del intercambiador est n clasificadas como sigue Importante Alerta que una acci n o procedi...

Page 31: ...fig 2 La placa del fabricante contiene la siguiente informaci n A Referencia del producto B Descripci n del producto C N mero de serie D Fecha de entrega a o y semana p e 1018 es decir a o 2010 seman...

Page 32: ...ema 2 Filtrar el aceite antes de su paso por el intercambiador Para conocer la compatibilidad de los flu dos reco mendados ver las Caracter sticas t cnicas Antes de la puesta en marcha Precauci n Aseg...

Page 33: ...de que el sistema est despresurizado 4 Desconectar la entrada y salida de aceite del radiador 5 Desconectar los flexibles hidr ulicos del radiador 6 Desatornillar los tornillos con arandelas que fijan...

Page 34: ...bien centrado y gira bien con la mano Ajustar si se cree necesario la posici n de la rejilla y del motor 8 Asegurarse de que los tornillos est n bien apretados 9 Conectar la fuente de alimentaci n el...

Page 35: ...ety distances to prevent hazard zones being reached by upper and lower limbs SS EN ISO 13857 2008 Electric motors used on the product comply with the Low Voltage Directive LVD 73 23 EEC of 19 February...