English
ETO2
13
© 2011 OJ Electronics A/S
RESTART
Restart operation. Keeping your current settings. The ETO2 will go to the initial
status display.
RESTART
When changing the settings or require a new process start, the ETO2 can be restarted in this menu.
OFFSET CALIBRATION
If it is necessary to calibrate the temperature measured by the ETOG sensor, please follow the steps
below:
1.
Disconnect the sensor from terminals 11 and 12 (sensor heating) of the ETO2.
2.
Wait a few hours until the sensor has acquired the same temperature as the ground.
3.
Measure the real ground/sensor temperature and compare it with the temperature shown on the
ETO2 display.
4.
Program the offset for the sensor concerned to match the difference between the two
temperatures (displayed/real). Adjust the necessary offset using the encoder button. Press OK.
5.
Reconnect the sensor to terminals 11 and 12 of the ETO2.
NOTE: With ETOG-55 sensor, the temperature shown on the ETO2 display is always the core
temperature of the sensor.
All manuals and user guides at all-guides.com
Summary of Contents for ETO2
Page 2: ...all guides com...
Page 8: ...all guides com...
Page 14: ...all guides com...
Page 20: ...all guides com...
Page 26: ...all guides com...
Page 32: ...all guides com...
Page 38: ...all guides com...
Page 44: ...all guides com...
Page 50: ...all guides com...
Page 56: ...all guides com...
Page 62: ...all guides com...
Page 68: ...all guides com...
Page 74: ...all guides com...
Page 80: ...all guides com...
Page 86: ...all guides com...
Page 92: ...all guides com...
Page 93: ...Fig 16 ETO2 77 2011 OJ Electronics A S All manuals and user guides at all guides com...
Page 94: ...ETO2 78 2011 OJ Electronics A S All manuals and user guides at all guides com...
Page 95: ...ETO2 79 2011 OJ Electronics A S All manuals and user guides at all guides com...