OJ EFS Series Instructions Manual Download Page 4

English

The EFS is applied when an accurate and
electrical noiseless regulation of major electrical
heating outputs is required, e.g. heating
surfaces in ventilation systems and industrial
plants. It can also be applied for regulation of
ceiling, floor and radiant heating etc. 

The EFS can be mounted in such a way that the
heat sink is being built into duct/Air Handling
Unit. 

The period time can be set between 1-40 secs.
which makes the EFS usable also for control of
infrared heating elements.

There are two variants of the EFS: EFS-9xx2 (2
thyristors) for installations with symmetrical load
and EFS-9xx3 (3 thyristors) for unsymmetrical
load. 

PRODUCT PROGRAM

Type

Product  

EFS-9252 Power controller  25A, 3x230V / 3x400V
EFS-9402 Power controller  40A, 3x230V / 3x400V
EFS-9632 Power controller  63A, 3x230V / 3x400V
EFS-9253 Power controller  25A, 3x230V / 3x400V

FUNCTION
The EFS is an electronic time proportional
power controller with two or three heavy
thyristor outputs with zero transition triggering
for 3-phased voltage.

The EFS transforms a signal to a pulse/pause
proportion of the switched on/off output. For
example if the control signal is 5V the output
will be switched on for 50% of the period time,
which is adjustable. Other types of control
signals can be used. The output is switched
on/off at the zero point of the sine curve thus
eliminating electrical noise on radios and TVs.

EFS has a built-in P and PI-controller and is
thus a compact power controller suitable for
controlling supply air temperature in ventilation
systems (figs 10-18) or for controlling underfloor
heating systems. EFS has a built-in signal
converter and can therefore be connected to an
external controller with voltage or current
output.

The EFS has a built-in relay, which makes it
possible to double the output by use of 2
heating elements of equal size (fig. 12-13).

CE MARKING
OJ declare under their own responsibility that
this product meets the requirements of the
European Council’s directive 89/336 and
successive modifications as to electro-magnetic
compatibility and the Council directive 73/23 as
to electrical equipment to be applied within
certain voltage ranges.

Standards applied 
EN 60 947-4-3.

The product may only be energised when the
entire installation meets the current directive
requirements.

When the product is installed according to this
instructions guide and the current installation
guidelines, it is covered by factory guarantee.

If the product has been exposed to damage e.g.
in transport, it must be checked and overhauled
by qualified staff before the product is
connected to the power.

SAFETY FUNCTIONS
Galvanic separation between output unit and
control signal.

Limit thermostat: 
The EFS has a built-in limit thermostat which
modulates the output load at excessive
temperature in the power controller, i.e. in case
of minor excessive temperature (the on-period
will be reduced), it is still possible to make a
regulation, but with reduced maximum output.
Active in the area 80˚C-85˚C.

Thermal fuse:
Furthermore the EFS has a thermal fuse which
zeroizes the control signal at internal
temperature above 90˚C. As soon as the
temperature is normal again, the control signal
will be switched on again automatically.

TECHNICAL DATA
INPUTS
Supply voltage  . . . . . . . . . . . . . . . . . .50-60 Hz, 

230/400V AC ±10%

Voltage signal  . . . . . . . . . . . . . . . . . . .0-10V DC
Voltage signal  . . . . . . . . . . . . . . . . . . .2-10V DC
Impedance (voltage signal) . . . . . . . . . .10K ohm
Current signal  . . . . . . . . . . . . . . . . . . . .0-20 mA
Current signal  . . . . . . . . . . . . . . . . . . . .4-20 mA
Voltage loss (current signal) . . . . . . . .1V (20 mA)

Outputs
Type EFS-9252  . . . . . . . . . . . . . . . .3x25A RMS
- primary fuse max. 1800A

2

S   . . . . . . . . . . . .25A

Type EFS-9253  . . . . . . . . . . . . . . . .3x25A RMS
- primary fuse max. 450A

2

S  . . . . . . . . . . . . .25A

Type EFS-9402  . . . . . . . . . . . . . . .3 x 40A RMS
- primary fuse max.1800 A

2

S  . . . . . . . . . . . .40A

Type EFS-9632  . . . . . . . . . . . . . . .3 x 63A RMS
- primary fuse max. 6300 A

2

S  . . . . . . . . . . . .63A

Further specifications
Output voltage  . . . . . . . . .Pulsating AC-voltage 

(PWM)

Output switch  . . . . . . . . . . . . .Thyristors 1200V
Protection against transients   . .Built-in varistors
Filter

 . . . . . . .Built-in filter 150K Hz - 30M Hz

Thermal fuse  . . . . . . . . . . . . . . . . . . . . . . . .90˚C
Temperature limit sensor  . . . . . . . . . .80˚C-85˚C 

(limits pulse width on the output 

voltage) and a fixed period 

time of 1-40 secs.

Supply output  . . . . . .+14V/25 mA for supply of 

external units (EFRP)

Relay output . . . . . . . . . . . . . .Voltage free SPST 

for two heating element system

Built-in 
P-controller  . . . . . . . Proportional controller with 

adjustable P-band 1-6°C and 

fixed period time of 20 sec

.

Built-in
PI-controller . . . . . . . . . . . . . . . PI-controller with 

adjustable P-band 1-6°C, 

fixed I-time of 8 min and 

fixed period time of 20 sec.

Temperature range  . . . . . . . . . . . . . . . . . .0-40˚C
Sensor input  . . . . . . . . .NTC-sensor (ETF-x99x)
Load form  . . . . . . . . . . . . . . .Star / delta, ohmic
Min. output load  . . . . . . . . . . . . . . . . . . . .400W
Power consumption  . . . . . . . . . . . . . . . . . . .5VA
Cos (PHI)  . . . . . . . . . . . . . . . . . . . . . . . . . . .0,98
Heat output

EFS-9xx2  . . . . . .approx. 2W/A
EFS-9xx3  . . . . . .approx. 3W/A

Insulation voltage . . . . . . . . . . . . . . .2500V RMS
Ambient temperature  . . . . . . . . . . . . .-10/+40˚C
Housing  . . . . . . . . . . . . . . . . . . . . . . . . . . .IP 20

MOUNTING AND CONNECTION
The EFS range is mounted on the wall or on
panel board

If it is required to mount the EFS on a DIN-rail
the bracket EFSA-5 is to be used.

By use of bracket EFSA-1 it is furthermore
possible to mount the EFS with the heat sink in
the duct. 

It must be secured that the controller is
sufficiently ventilated. Max. ambient
temperature at max output load 40˚C.

OUTPUT LOAD
A min. load between the phases of 400W is
required. In case of heavier output load than 3 x
63A for type EFS-9631 more EFS’es can be
parallelly coupled on the input (not on the
output).

CONTROL SIGNAL
The control cable from external controller can
be extended up to 50 m by a separate cable. It
must be avoid to place the cable parallelly with
other cables. Voltage signals may occur which
may interrupt the function of the controller.
Alternatively, an ETT-6 step controller can be
used. 

It is not necessary with a shielded cable to the
controller, however it improves the immunity of
the controller against noise, if it is being used in
industrial environment. The shield is connected
to terminal 13 (GND).

MOUNTING OF CONTROLLER
A.

Mount the controller according to
description.

B

Connect the cables according to
connection diagram, fig. 1-8.

C. Adjust the DIP-switches (see section 

DIP-switces)
see adjustment of input function

D. and connect the supply voltage.

Fig. 6.

Tilslutning av ekstern 4-20 mA
regulator.

Fig. 7.

Tilslutning av føler for intern regulator.

Fig. 8.

Tilslutning av ekstern regulator type 
EFRP-31

Fig. 9.

Tilslutning av ekstern regulator type 
EFRP-91

Fig. 10.  Tilluftstemperatur.
Fig. 11.  Tilluftstemperatur, fjerninnstilling av

settpunkt.

Fig. 12.  Effektfordobling
Fig. 13.  Effektfordobling, trinnrelé.
Fig. 14.  Romtemperatur.
Fig. 15.  Romtemperatur, settpunktforskyvning

±5 °C.

Fig. 16.  Romtemperatur, fjerninnstilling av

settpunkt. 

Fig. 17.  Romtemperatur, ekstern regulator.
Fig. 18.  Romtemperatur, ekstern regulator,

fjerninnstilling.

OJ Electronics A/S
Stenager 13B · DK-6400 Sønderborg
Tel. +45 73 12 13 14 · Fax +45 73 12 13 13
www.oj.dk · [email protected] 

4

Summary of Contents for EFS Series

Page 1: ...t limit termostat som glidende reducerer udgangseffekten ved overtemperatur i effektkontrolleren periodens on tid reduceres d v s ved mindre overtemperaturer vil der stadig kunne foretages en reguleri...

Page 2: ...skes en n yaktig og elektrisk st yfri regulering av st rre el varme effekter f eks varmeflater i ventilasjons og industrianlegg Kan ogs anvendes til regulering av gulv og takvarme samt radiator m m EF...

Page 3: ...2500V RMS Omgivelsestemperatur 10 40 C Kapsling IP 20 MONTERING OG TILSLUTNING EFS serien monteres p vegg eller p tavleplate Hvis EFS nskes montert p DIN skinne anvendes beslag 93226 Det er videre mul...

Page 4: ...cally TECHNICAL DATA INPUTS Supply voltage 50 60 Hz 230 400V AC 10 Voltage signal 0 10V DC Voltage signal 2 10V DC Impedance voltage signal 10K ohm Current signal 0 20 mA Current signal 4 20 mA Voltag...

Page 5: ...ION AGAINST EXCESSIVE TEMPERATURE E g in ventilation systems with electrical heating surfaces the system is supplied with a safety thermostat which via contacor will switch out the systemt if the the...

Page 6: ...as 1 ing ng 3 L2 Fas 2 Ing ng 5 L3 Fas 3 Ing ng 2 T1 Belastning 1 4 T2 Belastning 2 6 T3 Belastning 3 7 Kontaktor 8 Kontaktor Svagstr m styrsignal Plint Funktion 9 Str ming ng I in 10 Sp nningsing ng...

Page 7: ...une r gulation mais avec une sortie maximale r duite Le dispositif est actif dans la plage de 80 C 85 C Fusible thermique De plus le EFS est muni d un fusible thermique qui met z ro le signal de comma...

Page 8: ...dur e I est fix e 8 minutes R GULATEUR EXTERNE Quand EFS est r gl sur la fonction r gulateur externe DIP 4 un r gulateur externe standard peut tre utilis La p riode peut tre r gl e sur 1 40 s P2 VOYAN...

Page 9: ...0 80 85 1 40 14 V 25 mA SPST P 1 6 20 I PI P 1 6 I 8 20 0 40 C NTC ETF x99x 400 W 5 V s PHI 0 98 EFS 9 2 2 W EFS 9 3 3 W 2500 V RMS 10 40 C IP20 EFS DIN EFSA 5 40 C 400 V 3 63 EFS 9632 EFS 6 50 9 Dip1...

Page 10: ...dardowe sygna y wyj ciowe Prze czanie nast puje zawsze przy przej ciu sinusoidy przez zero co eliminuje zak o cenia elektryczne w sieci EPS posiada wbudowany regulator temperatury typu P oraz PI Dzi k...

Page 11: ...dr bnymi trasami Nale y unika prowadzenia tych kabli wspo lnie z innymi przewodami Skoki napi cia mog powodowa przerwy w dzia aniu regulatora EFS Nie jest niezb dne ekranowanie kabli sygna owych jakko...

Page 12: ...elektromagnetischer Kompatibilit t sowie auch der Direktive des Rats 73 23 betreffs Elektroausr stung zur Anwendung innerhalb gewissen Spannungsgrenzen entspricht Ber cksichtigte Standarde EN 60 947...

Page 13: ...den Periodezeit fest 20 Sek Die P Regelung wird mit DIP 3 eingestellt Interner PI Regler Bei DIP 3 Einstellung auf PI Regler ist die EFS Funktion gleich wie bei internem P Regler die Regelung erfolgt...

Page 14: ...ement triangular symmetrical Fig 3 Connection of heating element star unsymmetrical Fig 2 Connection of heating element star symmetrical Fig 4 Output doubling with built in relay Fig 5 Connection of e...

Page 15: ...r Fig 8 Connection of external controller type EFRP 31 Fig 7 Connection of sensor for internal controller Fig 9 Connection of external controller type EFRP 91 Fig 10 Supply air temperature Fig 11 Supp...

Page 16: ...remote setpoint setting Fig 15 Room temperature setpoint displacement 5 C Fig 13 Output doubling step relay Fig 12 Output doubling 16 5 7 9 2 8 A Fig 17 Room temperature external controller Fig 18 Roo...

Page 17: ......