4.9.2
4.9.2
Temperature deviation indicator
Temperature deviation indicator
Controller has three LED's, that operate in five steps and indicate the deviation of the
actual value from the set point. Each step operates for 2 % (4 °C) of full scale (0...200 ºC).
SIGNAL
MEANING
more than 6 °C below set value
6 - 2 °C below set value
Set value ± 2°C
2 - 6 °C above set value
more than 6 °C above set value
It is possible to modulate the temperature controller for 110 V voltage.
Contact Oilon technical support for further assistance.
4.10.
4.10.
Preheater limit thermostat settings
Preheater limit thermostat settings
4.10.1
4.10.1
Limit thermostat setting
Limit thermostat setting
The limit thermostat is adjusted at the factory and sealed with paint. Set value is +180°C .
The limit thermostat has a reset button. Use the reset when the limit thermostat is not
energized.
Do not open the sealed locking screw. Breaking the seal voids warranty
40 (57)
RPMARINES 30840641GB
4. First start-up and adjusting