Fault indications on a modulating burner
Fault indications on a modulating burner
SYMBOL
FAULT
CAUSE
Note
◄
Lockout
the CLOSE signal
has not been
delivered to terminal
8 from air damper
servomotor or
contact have not
been closed between
terminals 12 and 4 or
4 and 5.
◄
Lockout
Extraneous light (e.g.
non-extinguished
flame, leaking fuel
valves, defect flame
supervision circuit,
etc.).
▲
Interruption of start-
up sequence
the OPEN signal has
not been delivered to
terminal 8 from the
air damper
servomotor.
Terminals 6, 7 and
15 remain under
voltage until the fault
is corrected!
P
Lockout
Lockout because the
air pressure signal
has not been
received at the start
of the air pressure
control.
From this point on till
controlled shut down
every air pressure
failure triggers a
lockout. Too little
difference in air
pressure (<min.)
triggers a lockout
when differential air
pressure switch
connector (C/NC)
engages a control
signal to control unit
terminal 13.
■
Lockout
Fault in the flame
detection circuit
▼
Interruption of start-
up sequence
The ignition position
signal has not been
delivered to terminal
8 from air damper
servomotor
Terminals 6, 7 and
15 remain under
voltage until the fault
is corrected!