42 (67)
RE01 1445EN
Operating line number
(Heating circuit 1 /
heating circuit 2)
Function
721 / 1021
Heating curve displacement
If the curve slope is suitable for heating circuit but
the room temperature is constantly too low or high in
comparison to the set value, the temperature can be
changed from the operating lines.
‘+’ adjustment increases circulation setting and room
temperature
‘-’ adjustment decreases circulation setting and room
temperature.
730 / 1030
Summer/winter heating limit
Temperature when heating circulation is switched on/off.
Only operational in automatic mode.
740, 741 / 1040, 1041
Flow temp setpoint min, Flow temp setpoint max
Set the maximum and minimum temperature for heating
circuit supply water temperature range. This is a useful
way for example to limit supply water temperature
sufficiently low at floor heating locations. Floor heating
circuit maximum temperature should be limited to 40 °C.
A so called floor drying function can be carried out by
limiting maximum temperature to 18 °C.
Domestic hot water
Operating line number
Function
1610
Nominal setpoint
Domestic hot water temperature setting at nominal mode
(sun).
Summary of Contents for RE 35
Page 2: ......
Page 58: ...56 67 RE01 1445EN Wilo Stratos Para 25 1 12 WSP01 ver 1...
Page 59: ...RE01 1445EN 57 67 Wilo Stratos 40 1 12 WSP02a ver 1 WSP02b ver 1...
Page 60: ...58 67 RE01 1445EN Wilo IPL 40 115 0 55 2 WIPL03 ver 1...
Page 61: ...RE01 1445EN 59 67 Wilo IPL 50 115 0 75 2 WIPL02 ver 1...
Page 62: ...60 67 RE01 1445EN Wilo IPL 50 120 1 5 2 and Wilo IPL 50 130 2 2 2 WIPL01 ver 1...
Page 63: ...RE01 1445EN 61 67 Wilo Stratos Para 25 1 7 WSP03 ver 1...
Page 70: ...68 67 RE01 1445EN...
Page 71: ......