5.6 Burner automation description, gas use
Items marked with an asterisk (*) apply only if the burner is equipped
with an ignition gas valve.
Prerequisites for start
● All failures and interlocks reset.
● Burner flange limit switch closed.
● Safety loop closed.
● Boiler safety devices not activated.
● Control switch in position 1.
● Burner control in stand-by position.
● Manual or automatic mode selected in burner control. If automatic mode is selected,
the capacity controller must also be switched on.