43
・
Setting for maintenance timer o
Default: 1
Setting range: ,
This is to set the contact output behavior at the set maintenance notification time.
☞
See page 47 for assignment of alarm output terminals
:
Switchover of contact is disabled
:
Switchover of contact is enabled
*If this parameter is set at “ ”, no alarm output takes place at the set time although the display
shows “E4”.
・
Setting for assignment of alarm output terminals AS
Default: 0
Setting range: to 3
Alarm output terminals output once an alarm is detected. This is to assign the terminals for each
alarm.
☞
See page 47 for the assignment setting of alarm output terminals
: or monitoring of alarm occurrence
: or monitoring of cooling operation and alarm occurrence
:
or Identifying alarms that require power input and alarms that do not
3: or identifying alarms that continue cooling operation and alarms that do not
・
Choice of switching method for alarm output terminals Ao
Default: 0
Setting range: ,
This enables inversion of Open Close switching of output terminal.
☞
See page 47 for the assignment setting of alarm output terminals
: Output takes place as assigned for alarm output terminals by setting
: Reverse action to takes place, provided that this does not affect between terminals and 3
when AS setting is .
・
Setting of operation mode rM
Default: 1
Setting range: to 3
This is to set operation mode of COOLCABI.
☞
See pages 44 and 45 for operation modes
: Continuous run
: Energy saving mode
: Energy saving mode
3: Energy saving mode 3
・
Setting of cooling operation time for Energy saving mode 3 t
Default: 7
Setting range: 7 to 6 min
This is to set the cooling operation time when Energy saving mode 3 is selected.
・
Setting of shutdown time for external fan and compressor t
Default: 3
Setting range: 3 to min
This is to set the time for restarting compressor after shutdown. or prevention of frequent ON O
of the compressor, cooling operation is suspended during the set period.
・
Setting of communication address Ad
Default:1
Setting range: to 99
This is to set RS485 communication address.
・
Setting of communication speed br
Default:2
Setting range: to 4
This is to set communication speed.
:
48 bps
:
96 bps
:
9 bps
3
:
384 bps
4
:
576 bps
・
Setting of parity Pb
Default:2
Setting range: to
This is for parity setting.
: No parity
: Odd parity
: Even parity
・
Display of software version Sn
This is to show the software version. Unable to change the setting.
○
Hold down the SET button for more than 3 seconds when you finish the setting. The current internal
temperature is displayed again and the setting is saved.
○
When no button is pressed for 3 seconds during parameter setting, the setting is NOT SAVED and
the display shows the current internal temperature. To return to parameter setting, hold down the SET
button for more than 3 seconds.
Summary of Contents for COOL CABI OCA-H1000BC-AW2
Page 3: ...3 20 50 85 RH 0 60 85 RH R1234yf...
Page 4: ...4 2 1...
Page 6: ...6 8 9 COOLCABI...
Page 7: ...7 8 2 2 9 COOLCABI COOLCABI COOLCABI...
Page 12: ...12 30 ON OFF 1 6 ON OFF ON OFF 13 No Up UP Down Down Set...
Page 15: ...15 35 5 35 30 4 E 3 30 1 30 5 35 30 35 30 ON OFF ON OFF ON OFF ON OFF...
Page 16: ...16 7 3 5 5 45 35 30 30 ON OFF ON OFF ON OFF ON OFF 35...
Page 30: ...30 OCA H350BCD AW2 OCA H700BCD AW2 OCA H1300BCD AW2 OCA H2300BCD AW2 1...
Page 60: ...60 20 50 85 RH 20 60 85 RH R1234yf LFL 25 OFN...
Page 61: ...61 2 1...
Page 63: ...63 30 65 66 COOLCABI...
Page 64: ...64 65 2 2 66 COOLCABI COOLCABI COOLCABI...
Page 69: ...69 30 ON OFF 1 6 ON OFF ON OFF 70 Up UP Down Down Set...
Page 72: ...72 35 5 35 30 4 E 3 30 1 30 5 35 30 35 30 ON OFF ON OFF ON OFF ON OFF...
Page 73: ...73 t1 t2 7 3 5 5 45 35 30 30 ON OFF ON OFF ON OFF ON OFF 35...
Page 87: ...87 OCA H350BCD AW2 OCA H700BCD AW2 OCA H1300BCD AW2 OCA H2300BCD AW2 1...