33
−
Item
Upper
display
Description/setting range
Factory
setting
Heater high
alarm specified
temperature
n.
Heater high alarm specified
temperature Scaling range
100
Heater alarm
judgment lower
temperature
n.
Heater alarm judgment lower
temperature scaling range
100
Heater alarm
judgment upper
temperature
n.
Heater alarm judgment upper
temperature scaling range
1500
heater pause
alarm
n.
Use of heater pause alarm
: Not
used,
: Used
PA3 – 10 Multi PID
n: PID No. (n = 1 to 8)
Multi P
n.
Multi proportional band 0.1 to 999.9 % 2.0
Multi I
n.
Multi integration time 0.01 to 99.99 min. 3.00
Multi D
n.
Multi differentiation time 0.00 to 20.00
min.
0.00
Multi MR
n.
Multi manual reset 0 to 100%
50
PA11 Output limit
Output upper
limit
1st output upper limit
lower limit to 100
100
Output lower limit
1st output lower limit
0 to upper limit
0
2nd output upper
limit
2nd output upper limit
2nd output lower limit to 100
100
2nd output lower
limit
2nd output lower limit
0 to 2nd output upper limit
0
PA12 PV start
PV start
: Disabled,
: Enabled
PA13 Gapped control
Gap gain
0.01 to 0.50
0.01
Gap width
0 to 50%
0
7.3 Setup Screen
Item
Upper
display
Description/setting range
Factory
setting
SU1 Sensor
Input type
Refer to Input list (page 17)
Scaling H
Scaling upper limit value
TC or RTD input: Range, DC input:
−
1999 to
+
9999 (decimal point position
follows the setting.)
1370
Scaling L
Scaling lower limit value
TC or RTD input: Range, DC input:
−
1999 to +9999 (decimal point position
follows the setting.)
-200
Decimal point
Scaling value below decimal point 0 to 3 0
Summary of Contents for EC5500R