Parameter
Notation
Default
Value
Parameter Description
Range
0
O1TY
Output 1 signal type
: Relay
0
: Solid state relay drive
1
: Solid state relay
2
: 4-20 mA
3
4
: 0 - 20 mA
5
: 0 - 1V
6
: 0 - 5V
7
: 1 - 5V
8
: 0 - 10V
Output 1 function
0
OUT1
0
: Reverse (heating ) control
1
: Direct (cooling) control
O1FT
Output 1 failure transfer
mode
Select BPLS ( bumpless transfer ) or 0.0 ~
100.0 % to continue output 1 control function
as the unit fails, or select OFF (0) or ON (1) for
ON-OFF control.
0
O1HY
Output 1 ON-OFF control
hysteresis
Low: 0.1
High: 90.0° (
)
F 50.0°C
0.2 °F
(
)
0.1 °C
CYC1
Output 1 cycle time
Low: 0.1
High: 90.0 sec.
18.0
OFST
Offset value for P control
Low: 0
High: 100.0 %
25.0
RR
Ramp rate
0.0
Low: 0
(500.0 °C)
900.0 °F
High:
OUT2
Output 2 function
0
: Output 2 No Function
2
: Deviation High Alarm
3
: Deviation Low Alarm
6
: Process High Alarm
7
: Process Low Alarm
8
: Cooling PID Function
2
RAMP
Ramp function selection
0
: No Function
1
: Use unit/minute
2
: Use unit/hour
0
1
: Dwell timer action
4
: Deviation out of band Alarm
5
: Deviation in band Alarm
O2TY
Output 2 signal type
0
0
: Relay output
1
: Solid state relay drive
2
: Solid state relay
3
: 4 - 20 mA
4
: 0 - 20 mA
5
: 0 - 1V
6
: 0 - 5V
7
: 1 - 5V
8
: 0 - 10V
O2FT
Select BPLS ( bumpless transfer ) or 0.0 ~ 100.0 %
to continue output 2 control function as the unit
fails, or select ON (0) or OFF (1) for alarm and dwell
timer function.
Output 2 failure transfer
mode
0
CYC2
Output 2 cycle time
Low: 0.1
High: 90.0 sec.
18.0
O2HY
Output 2 hysteresis value
when output 2 performs
alarm function
Low: 0.1
High: (50.0 °C)
90.0 °F
0.2 °F
(0.1 °C)
CPB
Cooling proportional band
value
100
Low: 50
High: 300 %
Heating-cooling dead
band
(negative value = overlap)
0
Low: -36.0
High: 36.0 %
DB
11